Aprilaire 700 Humidifier Wiring Diagram

Aprilaire 700 Humidifier Wiring Diagram

Aprilaire 700 Humidifier Wiring Diagram

5/5 (1👤)
🌡️ HVAC & Water Heating 🧮 2 schematics
★Rate It★

How many stars do you give this diagram?

Aprilaire 700 wiring

Choose the control type; tap any terminal or component to see how it connects.

Aprilaire 700 wiring
NORTH, EAST ORWEST SIDE, ABOVETHE SNOW LINEHUMIDIFIERWATERDIGITAL HUMIDIFIER CONTROLRCABW/GCfODTHTRANSFORMER24 V ACCONTINUOUSLY POWERED(PROVIDED)24 V ACCESSORYCOMMONFURNACEOUTDOOR SENSOR(OR MANUAL MODERESISTOR)BROWN WIRES24 V AC120 V AC OUTLETHUMIDIFIERFURNACE BLOWER MOTORHILOWATERMANUAL CONTROLHUMIDIFIER CONTROLSOURCE24 V ACFURNACE ACCESSORY TERMINALSOR TRANSFORMER (10 VA MIN.)MODEL 50CURRENT SENSING RELAY(IF REQUIRED)TO FURNACECOMMONBROWN WIRES24 V AC120 V AC OUTLET

Terminals and components · 6

  • 24 V AC
  • Control
  • Outdoor sensor
  • Furnace signal
  • Humidifier
  • 120 V AC

About This Diagram

This diagram is redrawn from page 1 of the Aprilaire 700 Humidifier manual, and we offer it completely free and in English. We have also categorized it in the Humidifiers (HVAC & Water Heating) section on Diagramverse, and it has been rated by 1 user with an average rating of 5.0. If you have any specific questions about the Aprilaire 700 Humidifier Wiring Diagram, we suggest checking the Frequently Asked Questions (FAQs) section.

Printable Aprilaire 700 Wiring Diagrams

700 · Digital

1 / 2
Aprilaire 700 Humidifier Wiring Diagram – 700 · Digital
Aprilaire 700 Humidifier Wiring Diagram – 700M · Manual

Wiring Instructions

Before you start

First, work out which variant you have. The Aprilaire 700 · Digital tab is for the Model 700, which comes with a Digital humidifier control that mounts on the return duct and connects to an outdoor temperature sensor. The 700M · Manual tab is for the Model 700M, which uses a Manual humidifier control mounted on the return duct or on an interior wall. The two controls wire differently, so follow only the drawing that matches the control in your box.

Tools and materials:

  • Screwdrivers, wire strippers, a multimeter that reads AC volts, and a drill with a 3/4 in bit (the Digital control's sensor needs this hole)
  • Low-voltage control wire, which is not included. Standard 18 AWG thermostat cable is the usual choice. Use enough conductors for each run.
  • The supplied 24 V transformer and a Model 50 current sensing relay if your furnace needs one
  • A 120 V AC outlet for the humidifier power cord

Shut off power to the furnace at its switch or breaker and confirm it is dead with your meter. Turn the humidifier control to OFF. This humidifier should be installed by a qualified heating and air conditioning contractor. Installation must also meet local, state and federal codes. If a new 120 V outlet or circuit is needed, have a licensed electrician add it, and check whether your area requires a permit.

Step-by-step wiring

Model 700 (Digital):

  1. Mount the Digital humidifier control on the return duct so the RH sensor sits in the 3/4 in hole, with the gasket around the sensor cage.
  2. Run the 24 V transformer's secondary to R and C. The control must have power all the time, so feed the transformer primary from a constant 120 V source. Never connect it to the furnace blower circuit. You can take it from the hot 120 V AC line before that line enters the furnace.
  3. Mount the Outdoor temperature sensor on the north, east or west side of the house, above the expected snow line. Run two wires to the ODT terminals. Polarity does not matter.
  4. Connect W/G to the furnace's 24 V accessory terminal (often labeled HUM, ACC or EAC) and Cf to the furnace common. If those accessory terminals put out 120 V instead of 24 V, add a 24 V transformer. Check the furnace manufacturer's data for the voltage at those terminals and when they are powered.
  5. Connect the two H terminals to the humidifier's two brown wires. Polarity does not matter. Leave A and B empty.

Model 700M (Manual):

  1. Mount the Manual humidifier control. If it goes on the return duct, keep the foam gasket. If it goes on a wall, throw the gasket away and pick a spot away from drafts and heat sources.
  2. Connect one side of the 24 V source to Terminal 1 of the control. The source can be the furnace accessory terminals or a transformer rated at least 10 VA.
  3. Connect Terminal 2 to one of the humidifier's brown wires.
  4. Run the other brown wire through the Model 50 relay contact and back to the other side of the 24 V source. This closes the loop. The Model 50's current sensor goes around the blower motor's common wire. Wire the Model 50 only into the 24 V control loop, never into the transformer primary. If you use a transformer, it must not be fed from the blower circuit.
  5. If your furnace accessory terminals already switch 24 V with the blower, you may not need the Model 50. In that case the second brown wire goes straight back to the source.

Both models: Plug the humidifier fan's power cord into a 120 V AC outlet on a circuit other than the furnace motor circuit. Never connect the cord to a multi-speed blower motor or to a blower that doesn't run on 120 V AC.

Testing and start-up

  1. Open the saddle valve all the way, restore furnace power and plug in the humidifier.
  2. Check for about 24 V AC between R and C on the Digital control. It should be there whether or not the furnace is running. With the furnace running, check for about 24 V AC between W/G and Cf.
  3. Start a heat or fan call at the thermostat. On the Model 700, turn the knob to Test/Reset. You should hear the solenoid click and see the green Humidifier On light. The humidifier runs for only one minute in this mode. On the Model 700M, turn the knob to its highest setting.
  4. Let the unit run until water flows from the drain. Confirm the fan runs and every connection is tight and dry.
  5. Set the control to the right humidity level. On the Digital control, a dial setting of 5 is a good starting point. Don't leave the knob on Test/Reset.

Safety notes

  • The humidifier fan runs on 120 V AC. Always unplug the cord and shut off the furnace before you open the cover or touch any wiring.
  • Keep the 24 V wiring separate from 120 V conductors. Never connect the transformer secondary or the Model 50 contact to line voltage.
  • If you tap a hot water line, shut off the hot water first. Water above 125°F can scald instantly.
  • Route all wiring away from sheet metal edges and the hot surfaces of the furnace.

Troubleshooting

Symptom Probable Cause What to Check
Control display is blank or keeps resetting Transformer wired into the furnace blower circuit, or a loose R or C wire Measure between R and C. You should read about 24 V AC all the time, not only while the blower runs. Move the transformer primary to a constant 120 V source.
Humidifier never runs, even on Test/Reset No furnace signal at W/G and Cf With the furnace running, measure between W/G and Cf. You should read about 24 V AC. If not, confirm W/G is on the HUM, ACC or EAC terminal and Cf is on furnace common.
Fan spins but no water reaches the panel Brown wires not connected to H and H, or a loose spade connection Recheck both brown wires on the H terminals. During Test/Reset, measure for about 24 V AC across them and listen for the solenoid click. Also make sure the saddle valve is fully open.
Water flows but the fan doesn't turn Power cord not plugged in, or the outlet is dead Check for 120 V AC at the outlet. Make sure it isn't on the furnace motor circuit or behind a switch that is turned off.
Accessory terminal reads 120 V, or the control burned out Furnace accessory terminals put out line voltage, not 24 V Measure the accessory terminals. If they read 120 V, don't connect W/G or the manual loop directly. Add a 24 V transformer as shown.
Model 700M runs when the blower is off, or never runs Model 50 sensing the wrong wire, or installed in the transformer primary Check that the blower common wire passes through the Model 50 sensor and that its contact is wired in series in the 24 V loop only.
Manual control loop has no voltage 24 V source too small or not wired to Terminal 1 Measure for 24 V AC at Terminal 1. If you use a separate transformer, make sure it is rated at least 10 VA.
Red Service Required light flashes with an E code Wiring or sensor fault the control has detected Write down the code (E1 to E4). Power down and check the ODT wiring and all terminal screws. If the code comes back, call your contractor or Aprilaire Technical Support.
Windows fog up in cold weather on the Model 700 Outdoor temperature sensor disconnected or badly placed Check both ODT wires. Make sure the sensor is on a north, east or west wall, out of the sun and above the snow line.
Humidifier won't shut off H terminals shorted, or the furnace signal is miswired Turn the dial to OFF. If the unit keeps running, power down and look for a short between the brown wires or a bare wire touching another terminal.

Frequently Asked Questions (FAQs)


What is the difference between the Model 700 and the Model 700M wiring?
The Model 700 uses a Digital humidifier control, and the Model 700M uses a Manual humidifier control. The Digital control needs constant 24 V on R and C, an outdoor sensor on ODT, a furnace signal on W/G and Cf, and the brown wires on H and H. The Manual control is a simple switch wired in series with the humidifier valve in a 24 V loop. That loop often includes a Model 50 relay so the humidifier runs only while the blower runs.

Do I need the Model 50 current sensing relay?
You need the Model 50 only on the 700M, and only when your furnace has no 24 V accessory terminal that switches on with the blower. The relay senses current in the blower common wire and closes its contact only while the blower runs, so water can't flow while the fan is off. It is not included in the box. Your furnace's accessory terminal data tells you whether you need it.

Can I power the humidifier from the furnace blower circuit?
No. Plug the humidifier's power cord into a 120 V AC outlet on a circuit other than the furnace motor circuit. Don't connect it to multi-speed blower motors or to blowers that don't run on 120 V, because that can cause early component failure. The 24 V transformer must also stay off the blower circuit. You can, however, feed it from the hot 120 V line before that line enters the furnace.

How much current does the Aprilaire 700 draw?
The humidifier is rated at 120 VAC, 60 Hz and 0.8 A. That is a light load, and a standard general-purpose 120 V outlet can usually handle it alongside other small loads. Make sure the outlet is not on the furnace motor circuit. If you add a new outlet near the furnace, follow local code for the circuit and receptacle type.

What wire should I use for the 24 V connections?
Low-voltage control wire is not included, so you need to buy it. Standard 18 AWG solid thermostat cable is good general practice for the runs to the control, the outdoor sensor and the furnace. Pick a cable with enough conductors for each run. Keep the cable away from line-voltage wiring and hot furnace surfaces, and protect it where it passes sheet metal edges.

Where should the outdoor temperature sensor go?
Mount the outdoor temperature sensor on the north, east or west side of the house, above the expected snow line. Keeping it out of direct sun lets it read the true outdoor temperature. The control uses that reading to lower the humidity target as it gets colder outside, which keeps condensation off windows. Its two wires go to the ODT terminals in either order.

Can I run the Digital control without the outdoor sensor?
Yes. You can run the Digital control in Manual mode, with a manual mode resistor on the ODT terminals in place of the sensor and the internal switch set to MAN. An M appears on the display. In this mode you have to lower the setting yourself before cold weather arrives. At 20°F outside, for example, 35% RH is the recommended setting.

What are the A and B terminals on the Digital control for?
A and B aren't used in this standard Model 700 wiring, so leave them empty. They relate to other wiring options, such as letting the control turn on the HVAC blower when humidity is needed. If you use the Blower Activation feature, the humidifier must be plumbed to hot water. Check the control's own instructions for those other wiring options before you connect anything to A and B.

Does polarity matter on the brown wires or the ODT wires?
No, neither one has polarity. The two humidifier brown wires can go to either H terminal on the Digital control. On the 700M, one goes to the manual control and the other to the Model 50 or the source, in either order. The two outdoor sensor wires can also go to the ODT terminals either way. Polarity only matters for the R and C supply and the W/G and Cf signal pair.

Can I install the Aprilaire 700 on a heat pump or a downflow furnace?
Yes, with precautions. On a heat pump system, supply the humidifier with hot water, because the warmer water makes up for the cooler supply air. On a downflow furnace, set things up so the blower keeps running after a heat call ends. Otherwise heat can damage the control mounted on the duct. Don't mount the humidifier on ducts with horizontal airflow, because performance drops.

Related Product Diagrams

Go up