Honeywell Aquastat Relay L8148E Wiring Diagram
L8148E connections
Thermostat, 24 V gas valve, circulator and power; below, the internal schematic in gray.
Terminals and components · 8
- Thermostat
- Jumper
- L6006
- High limit
- Burner
- Circulator
- L1
- L2
- Ground
What it does
Energizes the L8148E relay: it closes the circulator circuit and, if the water is below the high limit, the burner circuit.
Setting
Set the thermostat heat anticipator at 0.2 A.
What it does
Carries 24 V from the internal transformer to the relay. Without it (and without an L6006), the L8148E won't respond to the thermostat.
What to do
Remove the Z–W jumper when adding the L6006 low limit controller: its R–W contact takes its place.
How to connect it
- L6006 W to terminal W.
- L6006 R to terminal Z.
- L6006 B to the high limit B terminal.
Before wiring
Remove the Z–W jumper.
What it does
It cuts only the burner: the circulator keeps running during the thermostat call for heat.
Setting
Follow the boiler manufacturer's recommendation. With the cover off, turn the dial until the setting is under the pointer; the dial stop is factory-set at the top of the scale and can be adjusted.
Warning
Use the L8148E only in systems with a pressure relief valve.
How to connect it
B1 goes to TR and B2 to TH on the gas valve (e.g., VR8300). THTR stays empty.
Ratings
Low voltage burner circuit: 0.8 A maximum at 24 V AC.
Caution
Never jumper or short terminals B1 and B2: it burns out the L8148E transformer.
Terminal B1
B1 is a 1/4 in. tab terminal: use 18–22 gauge wire with a fully insulated flag receptacle connector.
How to connect it
The two circulator leads go to C1 and C2. On a call for heat, the relay contact joins L1 to C1; C2 is tied to L2.
Contact rating
120 V AC 240 V AC Full load 7.4 A 3.7 A Locked rotor 44.4 A 22.7 A What it does
Feeds the internal transformer (which supplies 24 V for the thermostat and burner) and the circulator.
Protection
Provide a disconnect means and overload protection as required.
How to wire it
- Copper wire only; the terminals accept wrap-around wiring only.
- Strip 7/16 in. and wrap the wire at least 3/4 of the way around the screw.
- Tighten until the wire contacts the plate, then one-half turn more (no push-type ratchet screwdriver).
What it does
Completes the 120 V circuit. C2 is tied to L2 inside the L8148E.
Protection
Provide a disconnect means and overload protection as required.
What it does
Connects the L8148E metal case to earth ground with the grounding screw provided.
Required
The control case must be connected to earth ground.
Three zones with V8043F valves
T87F thermostats, V8043F valves and one circulator; the third valve has its own transformer.
Terminals and components · 10
- Thermostats
- 24 V (W)
- Valve motor
- Jumper
- End switches
- Additional transformer
- Burner
- Circulator
- Power
- Ground
How to connect it
- One terminal of each thermostat goes to its valve's TR terminal.
- Zones 1 and 2: the other terminal goes to W on the L8148E.
- Zone 3: the other terminal goes to the additional transformer.
Capacity
The L8148E powers two V8043 zone valves, or only one when the ambient temperature exceeds 77 °F (25 °C).
Maximum load
1.4 A at 24 V AC; 1.2 A above 77 °F (25 °C) ambient. Use additional transformers when the load exceeds this.
Models with SV9500/SV9600
If a 50 VA L8148E powers an SV9500/SV9600 valve, the zone valves need a separate transformer.
How to connect it
TR goes to the zone thermostat. TH is jumpered to the end switch terminal that goes to TV (in zone 3, TH also goes to the additional transformer).
TH-TR
In this hookup the TH-TR terminal stays empty.
What it does
This ties TH to the end switch terminal that goes to TV on the L8148E.
What it does
The end switch closes when the valve is fully open. It acts as the L8148E thermostat: one open zone is enough.
How to connect it
The zone 3 thermostat and its valve's TH terminal go to the 24 V secondary; the primary goes to L1 and L2.
Rule
Use one additional transformer for each group of up to two valves.
Protection
Provide a disconnect means and overload protection as required.
Ratings
Low voltage burner circuit: 0.8 A maximum at 24 V AC.
Caution
Never jumper or short terminals B1 and B2: it burns out the L8148E transformer.
Terminal B1
B1 is a 1/4 in. tab terminal: use 18–22 gauge wire with a fully insulated flag receptacle connector.
How to connect it
A single circulator for all zones: its two leads go to C1 and C2.
Contact rating
120 V AC 240 V AC Full load 7.4 A 3.7 A Locked rotor 44.4 A 22.7 A What it does
Powers the L8148E: L1 is the hot leg and L2 the neutral of 120 V AC.
Protection
Provide a disconnect means and overload protection as required.
What it does
Connects the L8148E metal case to earth ground with the grounding screw provided.
Required
The control case must be connected to earth ground.
Zoning with R845 relays
Each zone has its own thermostat and R845 relay; the relays call the L8148E for heat through T and TV.
Terminals and components · 8
- Thermostats
- Relays
- Pumps / circulator
- Heat call
- Jumper
- Burner
- L1
- L2
- Ground
How to connect it
Each thermostat goes only to its relay. The relay has its own transformer: the thermostat does not go to the L8148E.
Terminals
Terminal Goes to 1 · 3 L1 2 L2 4 Zone pump 5 · 6 L8148E TV and T Terminals
Terminal Goes to 1 L1 2 L2 and circulator 3 L8148E C1 4 Circulator 5 · 6 L8148E T and TV More zones
The other R845A relays connect the same way: the arrows at the top carry TV, T, C1, L1 and L2 to each relay.
What it does
The relay's 3-4 contact feeds it L1 when its zone calls for heat. The L8148E C1 and C2 stay empty.
How to connect it
C1 goes to R845A terminal 3 (and terminal 3 of the other relays); terminal 4 goes to the zone circulator, whose other lead goes to terminal 2 (L2). C2 stays empty.
Contact rating
120 V AC 240 V AC Full load 7.4 A 3.7 A Locked rotor 44.4 A 22.7 A What it does
With any zone calling for heat, the L8148E fires the burner (if the water is below the high limit).
What it does
Carries 24 V from the internal transformer to the L8148E relay.
Ratings
Low voltage burner circuit: 0.8 A maximum at 24 V AC.
Caution
Never jumper or short terminals B1 and B2: it burns out the L8148E transformer.
Terminal B1
B1 is a 1/4 in. tab terminal: use 18–22 gauge wire with a fully insulated flag receptacle connector.
What it does
Feeds the L8148E, each relay's transformer (terminal 1) and each pump contact (terminal 3).
Protection
Provide a disconnect means and overload protection as required.
What it does
Feeds the L8148E and each relay's transformer (terminal 1).
Protection
Provide a disconnect means and overload protection as required.
What it does
120 V return for the L8148E, the relays and the pumps.
Protection
Provide a disconnect means and overload protection as required.
What it does
Connects the L8148E metal case to earth ground with the grounding screw provided.
Required
The control case must be connected to earth ground.
Zoning with R882C relays
Three zones with one circulator each, switched by R882C relays powered from the L8148E.
Terminals and components · 9
- Thermostats
- Z (24 V)
- Coils
- Heat call
- Circulators
- Jumper
- Burner
- Power
- Ground
How to connect it
One terminal of each thermostat goes to Z on the L8148E (all three in parallel) and the other to coil terminal B on its relay.
Capacity
The L8148E powers up to three R882C relays. Each additional group of up to three relays needs another transformer.
L8148J
The L8148J wires the same way; it also has TP and B3 terminals.
What it does
On a call for heat, the coil closes the upper contact (heat call to the L8148E) and the lower one (zone circulator).
Enclosure
The R882C comes with an NEC Class 1 enclosure.
What it does
Acts as the L8148E thermostat: with one zone calling, it fires the burner (if the water is below the high limit). N.C. stays empty.
How to connect it
C1 goes to each relay's lower N.O. contact; its COM. goes to the zone circulator, whose other lead returns to C2.
Contact rating
120 V AC 240 V AC Full load 7.4 A 3.7 A Locked rotor 44.4 A 22.7 A What it does
Joins W and Z so the internal transformer powers the L8148E relay and the zone thermostats.
Ratings
Low voltage burner circuit: 0.8 A maximum at 24 V AC.
Caution
Never jumper or short terminals B1 and B2: it burns out the L8148E transformer.
Terminal B1
B1 is a 1/4 in. tab terminal: use 18–22 gauge wire with a fully insulated flag receptacle connector.
What it does
Powers the L8148E: L1 is the hot leg and L2 the neutral of 120 V AC.
Protection
Provide a disconnect means and overload protection as required.
What it does
Connects the L8148E metal case to earth ground with the grounding screw provided.
Required
The control case must be connected to earth ground.
D892/M892 vent damper
Intermittent pilot system with a vent damper: through the S8610 module or plugged into the L8148E.
Terminals and components · 8
- Thermostat
- Jumper
- Ignition module
- VR8304
- Vent damper
- Circulator
- Power
- Ground
What it does
On a call, the L8148E runs the circulator and passes the call to the burner circuit.
Setting
Set the thermostat heat anticipator at 0.2 A.
What it does
Carries 24 V from the internal transformer to the L8148E relay.
How to connect it
L8148E S8610 Z 24V B1 TH-W B2 24V GND Caution
Follow the wiring carefully: miswiring could result in constant on.
Caution
Never jumper or short terminals B1 and B2: it burns out the L8148E transformer.
Terminal B1
B1 is a 1/4 in. tab terminal: use 18–22 gauge wire with a fully insulated flag receptacle connector.
How to connect it
Each valve terminal goes to the matching S8610 terminal: MV to MV, PV/MV to MV/PV and PV to PV.
How to connect it
The damper wiring harness plugs into the S8610 VENT DAMPER PLUG socket.
Caution
Remove the S8610 plug only if using a vent damper. With the damper connected, a fuse in the module blows when the thermostat first closes; from then on the module works only with the damper connected.
How to connect it
The 197516A cable joins the damper's 4-prong connector to the L8148E 6-prong Molex receptacle (5-prong plug on the cable). Only some L8148E models have this receptacle.
Before plugging in
Remove the plug-in that jumpers receptacle pins 2 and 3.
Fuse
After the damper is plugged in, a fuse in the L8148E blows when the thermostat first closes. From then on the L8148E works only with the damper connected.
What it does
The module gets the 24 V heat call through B1 and B2, via the high limit and the damper.
Caution
Never jumper or short terminals B1 and B2: it burns out the L8148E transformer.
Terminal B1
B1 is a 1/4 in. tab terminal: use 18–22 gauge wire with a fully insulated flag receptacle connector.
How to connect it
The two circulator leads go to C1 and C2.
Contact rating
120 V AC 240 V AC Full load 7.4 A 3.7 A Locked rotor 44.4 A 22.7 A What it does
Powers the L8148E: L1 is the hot leg and L2 the neutral of 120 V AC.
Protection
Provide a disconnect means and overload protection as required.
What it does
Connects the L8148E metal case to earth ground with the grounding screw provided.
Required
The control case must be connected to earth ground.
About This Diagram
These diagrams are redrawn from pages 8–11 of the Honeywell Aquastat Relay L8148E manual, and we offer them completely free and in English. We have also categorized it in the Capacitors, Contactors & Relays (HVAC & Water Heating) section on Diagramverse, and it has been rated by 1 user with an average rating of 5.0. If you have any specific questions about the Honeywell Aquastat Relay L8148E Wiring Diagram, we suggest checking the Frequently Asked Questions (FAQs) section.
Printable Honeywell Aquastat Relay L8148E Wiring Diagrams
Wiring Instructions
Before you start
First, pick the Honeywell Aquastat Relay L8148E tab that matches your system. Use Complete for a single-zone boiler controlled by one 24 V thermostat. Inside it, choose the With L6006 low limit variant only if you are adding an L6006 low limit controller. Use Zone valves for V8043F valve zoning. Use R845 relays when each zone has its own pump (One pump per zone) or when an R845A switches the circulator (Switched circulator). Use R882C relays when R882C relays switch the zone circulators. Use Vent damper when a D892/M892 damper is fitted, either through an S8610 module or plugged straight into the L8148E.
Gather an insulated flat-blade screwdriver, a wire stripper, a non-contact voltage tester and a multimeter that reads AC volts and continuity. Do not use a push-type ratchet screwdriver. Use copper wire only, because the terminals are approved for copper and accept wrap-around connections only. If a wire lands on the 1/4 in. tab of terminal B1, use 18 to 22 gauge wire with a fully insulated flag receptacle connector. Size the 120 V conductors for the branch circuit and the circulator according to local code. The circulator contact is rated 7.4 A full load and 44.4 A locked rotor at 120 V, so check the pump nameplate against those figures.
Shut off power at the boiler disconnect, lock or tag it, and confirm with your tester that L1, L2, C1 and C2 are dead before you remove the cover. Confirm that the boiler has a pressure relief valve: this control must not be used without one. The installer should be a trained, experienced service technician. Work on boilers, gas valves and line voltage usually requires a licensed professional, and often a permit, so check your local rules.
If you are replacing an old control, tag every lead before you disconnect it, using the old control's cover insert as a guide. Add up the 24 V load. It must not exceed 1.4 A, or 1.2 A if the boiler room is warmer than 77°F. The burner circuit itself is limited to 0.8 A at 24 V AC.
Step-by-step wiring
- Mount the control on its immersion well. Push the bulb in until it bottoms, use heat-conductive compound if the bulb fits loosely, and center the loop of excess capillary tubing so it cannot touch any electrical part.
- For every screw terminal, strip 7/16 in. of insulation, wrap the wire at least three quarters of the way around the screw, tighten until snug, then give it another half turn.
- Connect the equipment ground to the case using the grounding screw provided.
- Run 120 V AC from a disconnect with overload protection: hot to L1 and neutral to L2. Bring the cable through the 1/2 in. conduit knockouts.
- Wire the circulator to C1 and C2. In the zoning tabs, C1 feeds the relay contacts instead: R845 terminal 3 in Switched circulator, or the lower N.O. contact of each R882C.
- Wire the burner circuit. On a standard 24 V gas valve, B1 goes to TR and B2 goes to TH. In the Vent damper tab, B1 goes to TH-W on the S8610 (or 24V on the S8600) and B2 goes to 24V GND.
- Wire the heat call to T and TV. This can be the room thermostat, the valve end switches in parallel, R845 contacts 5-6 in parallel, or the upper R882C contacts (N.O. to TV, COM. to T). Set the thermostat's heat anticipator to 0.2 A.
- Leave the Z–W jumper in place unless you are installing an L6006. In that case, remove the jumper and connect the L6006 W to W, R to Z, and B to the high limit B.
- For zone valves, power no more than two V8043 valves from W, add the TH jumper on each valve, and give any further valves their own transformer. For R882C zoning, power no more than three relays from the L8148E.
- For a vent damper, remove the plug-in that jumpers pins 2 and 3 only when you are actually connecting the damper, then seat the 197516A cable or the S8610 damper plug fully.
- Set the high limit dial to the boiler manufacturer's recommendation, then refit the cover.
Testing and start-up
Restore power and measure about 120 V AC between L1 and L2. With the thermostat satisfied, nothing should run. Raise the thermostat setting. You should hear the relay pull in, the circulator should start, and the gas valve should receive roughly 24 V AC across TR and TH so that the burner lights, provided the boiler water is below the high limit. Next, turn the high limit dial below the current boiler temperature: the burner should stop while the circulator keeps running. Return the dial to its setting afterward. Test each zone on its own, then watch the system through at least one complete heating cycle. With a vent damper, the burner should fire only after the damper has opened.
Safety notes
- L1, L2, C1 and C2 carry 120 V in the same case as the 24 V terminals. Keep low voltage conductors routed away from line voltage conductors.
- Never jumper or short B1 and B2: doing so burns out the internal transformer.
- Connecting a vent damper to the L8148E permanently blows an internal fuse on the first call for heat. Do this only when the damper is a permanent part of the system.
- Do not exceed the ratings above, and never run the boiler without a working pressure relief valve.
Troubleshooting
| Symptom | Probable Cause | What to Check |
|---|---|---|
| Nothing happens when the thermostat calls for heat; no relay click | No 120 V supply, Z–W jumper missing, or thermostat leads not on T and TV | Measure 120 V AC between L1 and L2. Confirm that the Z–W jumper is in place, or that the L6006 is wired in its place. Check that the thermostat wires are tight on T and TV. |
| The control went dead right after work on the burner wiring | B1 and B2 were shorted or jumpered, burning out the transformer | Inspect the burner wiring for a short between the B1 and B2 leads or at the gas valve. A burned-out transformer means replacing the control. |
| The pump runs but the burner never lights | B1 or B2 is loose or on the wrong valve terminal, the boiler is above the high limit, or the tab connector on B1 is not seated | During a call, measure about 24 V AC across TR and TH on the gas valve. Confirm B1 goes to TR and B2 to TH, the flag connector is fully pushed onto B1, and the high limit dial is above the boiler temperature. |
| The burner fires but the circulator never starts | Loose C1 or C2, missing neutral to the pump, or C1 not routed through the relay contacts in zoned systems | During a call, measure 120 V AC across the circulator leads. In Switched circulator, check C1 to R845 terminal 3. With R882C relays, check C1 to the N.O. contacts and the return to C2. |
| The burner or pumps run constantly even with all thermostats satisfied | Shorted thermostat cable, or end switches or relay contacts wired across the wrong terminals | Lift the wire from T. If everything stops, the fault is external: check the thermostat cable, the end switches, R845 contacts 5-6 and the R882C N.O. and COM. connections. |
| The boiler stopped working once the vent damper was unplugged | The internal fuse blew on the first call after the damper was connected, which is by design | Reconnect the D892/M892 and make sure the 197516A cable, or the S8610 damper plug, is fully seated at both ends. From then on, the system works only with the damper connected. |
| Zone valves open slowly or not at all, and the control runs hot | Too many valves on the internal transformer | Power no more than two V8043 valves from W, or one if the room is above 77°F. Move the extra valves to their own transformer, with a maximum of two per transformer. |
| One zone's valve opens but the boiler never fires for that zone | Missing TH jumper on that valve, or its end switch not wired in parallel to T and TV | Add the jumper from TH to the end switch, then check continuity across that valve's end switch leads at T and TV with the valve open. |
| The L6006 is installed but has no effect on boiler temperature | Z–W jumper left in place, or L6006 leads swapped | Remove the Z–W jumper. Verify L6006 W to W, R to Z and B to the high limit B. |
| Room temperature overshoots or the burner short-cycles | Thermostat anticipator set wrong, or bulb not bottomed in the well | Set the anticipator to 0.2 A. Reseat the bulb against the bottom of the well, using heat-conductive compound if it fits loosely. |
| Wires work loose or terminals show scorch marks | Non-copper wire, wire wrapped the wrong way or too little, or terminals undertightened | Use copper only. Strip 7/16 in., wrap at least three quarters around the screw, tighten until snug, then add a half turn with a hand screwdriver. |
| You feel a tingle from the case or the boiler controls behave erratically | Case ground missing or loose | With power off, check continuity between the grounding screw and the equipment ground. You should read near 0 ohms. |