Dometic Duo Therm RV Thermostat Wiring Diagram

Dometic Duo Therm RV Thermostat Wiring Diagram

Dometic Duo Therm RV Thermostat Wiring Diagram

5/5 (1👤)
🌡️ HVAC & Water Heating 🧮 4 schematics
★Rate It★

How many stars do you give this diagram?

Typical dual basement wiring

Electric box with the two 115 V circuits, the Comfort Control Center field wiring and the 9-pin connectors to the unit.

Typical dual basement wiring
FIELD WIRINGELECTRIC BOX9-PIN CONNECTORSSTAGE 1 · FIELD WIRINGSTAGE 2 (OPTIONAL)RUN CAP 1PTCRRUN CAP 2PTCRRELAYS, CAPACITORSAND PTCRfactory wiringopenopenMAIN UNIT · FACTORY WIRINGopenopenHR 1HR 2FB1FB2TERM. BLK 1CIR. #1115 V AC · 60 Hz · 1 PHCopper conductors onlyL1BLKGRG-YNWHTTERM. BLK 2CIR. #2115 V AC · 60 Hz · 1 PHCopper conductors onlyL1ORNGRG-YNGRYG-YP1P2P3P4P5CB1AC POWER MODULEP6P1P2P3P4P5CB2AC POWER MODULEP6DIPDIPF1 · 3 AF1 · 3 ACOMFORT CONTROLphone cableBLK+12 VRED−12 VBLKFURNACEBLUFURNACEBLULOAD SHEDYELLOAD SHEDYELFURN. BLOWERBLKFURNACEBLUFURNACEBLUBLKWHTREDWHTBRNBLKREDVIOVIOORNGRYBRNWHTBRNBLKRED123456789CIR. #1To 9-pin connectorat field connect boxon main unit123456789CIR. #2To 9-pin connectorat field connect boxon main unitCIR. #1123456789BLKCWHTRREDSCOMPRESSORWHTBRNBLKREDMFANMOTORVIOVIOREVERSING VALVE(two solenoids)HEAT PUMP MODELS ONLYCIR. #2123456789ORNCGRYRBRNSCOMPRESSORWHTBRNBLKREDMFANMOTOR

Terminals and components · 18

  • Line and +12 V
  • Neutral and common
  • Ground
  • Communication
  • Furnace
  • Compressor
  • Fan motor
  • Reversing valve
  • Field wiring

About This Diagram

These diagrams are redrawn from pages 52–54 of the Duo Therm RV Thermostat User Manual, and we offer them completely free and in English. We have also categorized it in the Thermostats (HVAC & Water Heating) section on Diagramverse, and it has been rated by 1 user with an average rating of 5.0. If you have any specific questions about the Dometic Duo Therm RV Thermostat Wiring Diagram, we suggest checking the Frequently Asked Questions (FAQs) section.

Printable Dometic Duo Therm RV Wiring Diagrams

Complete · Heat pump · 39424

1 / 4
Duo Therm RV Thermostat Wiring Diagram – Complete · Heat pump · 39424
Duo Therm RV Thermostat Wiring Diagram – Complete · Air conditioner · 39224
Duo Therm RV Thermostat Wiring Diagram – 9-pin check
Duo Therm RV Thermostat Wiring Diagram – AC module

Wiring Instructions

Before you start

This diagram covers the Duo-Therm Comfort Control Center on a dual basement system: one electric box with two AC power module boards, CB1 and CB2, each running its own compressor and fan. Pick the variant that matches the model number on the rating plate. 39424 is the dual basement heat pump and 39224 is the dual basement air conditioner. The 9-pin check tab is for testing the two 9-pin connectors on these dual units. The AC module tab is for a single basement heat pump, which has only one board, so use it only if you have a single-compressor unit.

  • Tools: insulated screwdrivers, wire stripper, RJ-11 crimping tool, a voltmeter that reads AC and DC, an ohmmeter, a clamp-on ammeter and a 115 V incandescent test bulb with leads.
  • Power wiring: each unit needs two separate 115 V AC, 60 Hz circuits, CIR 1 and CIR 2. Protect each one with its own 15 A time-delay fuse or 15 A HACR breaker. Use copper conductors only. 12 AWG copper with ground is the usual run for these units. Confirm the size against the circuit length and your local code.
  • 12 V DC wiring: run a dedicated 18–22 AWG line from the RV converter or battery. The control works between 10 and 30 V DC.
  • Communication cable: flat 4-conductor, 26 gauge stranded copper (yellow, green, red, black) with a 4-position RJ-11 plug. Do not use a pre-made telephone extension cord.
  • Isolation: switch off both 115 V AC breakers, unplug shore power, stop the generator and disconnect the battery positive. Then confirm with your meter that no AC voltage is present.
  • Professional help: this equipment must be serviced by qualified personnel, and some states require that person to be licensed. All wiring must comply with national, state and local codes. If you are not comfortable working on 115 V branch circuits, have an electrician run the two supply circuits.

Step-by-step wiring

  1. Mount the Comfort Control Center 54 inches above the floor on an inside partition. Keep it away from sunlight, lamps, outside doors, windows and supply registers. If you use a remote sensor, mount the sensor to these rules instead.
  2. Make up the phone cable. Cut both ends square, strip only the outer jacket, and insert the conductors so the black wire is on your left when you look at the top of the plug with the spring clip facing you. Crimp both ends the same way. Plug one end into the Comfort Control Center and the other into CB1. Leave the factory link from CB1 to CB2 in place.
  3. Run the circuit 1 supply to the CIR 1 terminal block: L1 BLK, N WHT and GR G-Y. Run the circuit 2 supply to CIR 2: L1 ORN, N GRY and GR G-Y. Keep the two circuits on their own breakers and never swap them.
  4. Connect the 12 V DC supply to connector P6 on CB1: 12V+ RED and 12V− BLK. Check the polarity before you energize.
  5. Connect the two BLU furnace thermostat wires from the gas furnace to P6 on CB1. If your furnace supports a second stage, land its two BLU wires on P6 of CB2.
  6. Optional: connect the two YEL load shed wires to P6 on CB1. The energy management system must supply a normally open relay contact that closes when it wants the compressor off.
  7. Optional: wire the furnace blower through relays FB1 and FB2. This circuit does not work with every furnace, so confirm the connection with the furnace manufacturer first.
  8. Set the DIP switches with the Comfort Control Center switched OFF. On CB1, set every DIP switch OFF. On CB2, set the STAGE DIP (#2) ON and all others OFF.
  9. Plug in the sensors. On the 39424 heat pump, plug an ambient sensor into P3 (red) on each board. If you use a remote sensor, plug it into P4 (white). Leave P5 (blue) empty, because the freeze control is not used on basement units.
  10. Join the two 9-pin connectors (CIR #1 and CIR #2) between the electric box and the main unit's field connect box. Make sure they are fully seated and every pin is tight.

Testing and start-up

  • With the unit OFF, measure AC voltage at each terminal block, then measure again under load. Both readings must stay between 103 and 126.5 V AC. Correct the supply before you run the system if they don't.
  • Measure the incoming DC between RED (+) and BLK (−). It should read 10 to 30 V and must never exceed 30 V.
  • Check the F1 3 A fuse on each board with a DC voltmeter, from negative to each side of the fuse. You should see voltage on both sides.
  • Switch the Comfort Control Center ON. The display should light and show only the modes your installation supports. Select COOL and lower the setpoint. The compressor should start after about 2 minutes. Circuit 2 starts after circuit 1, and only once the stage differential is reached.
  • On a 39424, select HEAT PUMP and confirm the reversing valve switches. In heat mode, the line at the top of the inside coil should feel warm.
  • Use a clamp-on ammeter on each black supply wire to record the current draw, which tells you whether a breaker is tripping too early.

Safety notes

  • The box contains two separate 115 V circuits, so turning off one breaker does not make it safe. Open both and verify zero volts at CIR 1 and CIR 2.
  • Run and start capacitors can hold a charge after the power is off. Discharge them before you touch their terminals.
  • Connecting or disconnecting components with 12 V DC applied can blow F1. Remove the DC power first.
  • Live tests with the test bulb are energized-circuit work. Only a qualified technician should do them.
  • Bond every ground (G-Y) to the casing ground, and never use the neutral as a ground.

Troubleshooting

Symptom Probable Cause What to Check
Display stays blank when I turn the control ON No 12 V DC, reversed 12V+/12V− polarity, blown F1 fuse, or a bad phone cable Measure DC between RED (+) and BLK (−) at P6. It should read 10 to 30 V. Check F1 with a DC voltmeter for voltage on both sides. Confirm the cable has black on the left at both plugs, then run the reset procedure.
Control lights up but the unit does nothing, or acts erratically Store-bought extension cable with reversed polarity, or the phone cable plugged into CB2 instead of CB1 Replace the cable with a hand-crimped 4-conductor 26 gauge cable made the same way at both ends. Plug the Comfort Control Center into CB1.
First compressor runs but the second never starts STAGE DIP (#2) not ON on CB2, no power on CIR 2, or the stage differential not reached yet Turn the control OFF and set STAGE DIP #2 ON on CB2 only. Check for 103 to 126.5 V AC at CIR 2. Wait for the delay and check the differential setpoint.
Both compressors try to start at once, or the boards behave strangely STAGE DIP set ON on CB1 as well, or other DIP switches left ON Set every DIP on CB1 OFF and only STAGE (#2) ON on CB2, with the control switched OFF.
Breaker trips when a compressor starts Both compressors fed from one circuit, CIR 1 and CIR 2 swapped, low voltage, or the wrong breaker type Confirm circuit 1 lands on CIR 1 and circuit 2 on CIR 2, each on its own 15 A time-delay fuse or HACR breaker. Measure voltage under load and clamp the black wire for current draw.
Compressor won't come on at all, no hum Load shed contact closed, loose 9-pin connector, or the furnace mode selected Disconnect the YEL load shed wires and retest. Check the 9-pin pins are tight. Bulb-test pin 4 to pin 1, which should light when the compressor is called.
Fan only runs on one speed Loose wire at pin 6 or 7 of the 9-pin connector, or an open motor winding Bulb-test pin 4 to pins 6 and 7. With the power off, check continuity from WHT (pin 4) to BLK and RED and check the motor isn't grounded to G-Y.
Heat pump blows cold air in heat mode Reversing valve not powered, missing ambient sensor, or the air conditioner variant wired as a heat pump On the 39424, bulb-test pin 4 to pin 9 in heat mode, which should light. Check the solenoid reads about 465 ohms ±10%. Confirm the ambient sensor is in P3 (red).
Heat pump shuts off or switches to the furnace in cold weather Normal low-temperature lockout below 24°F, or a faulty ambient sensor Unplug the red P3 plug and measure ohms. It should read about 7876 ohms at 70°F, ±10%. Replace the sensor if the reading is out of range.
Room temperature overshoots or the unit cycles constantly Remote sensor not in P4, or the sensor or control mounted near a register, an outside wall or in the sun Plug the remote sensor into P4 (white). Relocate it 54 inches high on an inside partition, away from supply air.
Furnace blower doesn't run with the compressor The furnace doesn't support the FB1/FB2 blower circuit, or the field wire is loose Check the furnace manufacturer's connection instructions. Verify the BLK field wire at FB1 and FB2.

Frequently Asked Questions (FAQs)


How do I know which diagram variant matches my unit?
Read the model number on the rating plate, which you can see after removing the return air grille. 39424 is the dual basement heat pump and 39224 is the dual basement air conditioner. Both use two boards and two 9-pin connectors. On the heat pump, pins 8 and 9 of circuit 1 drive the reversing valve and each board has an ambient sensor. If your unit has only one compressor and one board, use the single basement heat pump module check instead.

Can I use a regular telephone extension cord for the control cable?
No. Pre-made telephone extension cords have reversed connector polarity, and the system will fail. Make your own cable from flat 4-conductor, 26 gauge stranded copper wire with 4-position RJ-11 plugs. Crimp each plug with the black wire on your left as you look at the top of the plug with the spring clip facing you. Both ends must match.

Why does a dual basement unit need two 115 V circuits?
Each compressor has its own board and its own supply. Circuit 1 feeds CB1 and compressor 1, and circuit 2 feeds CB2 and compressor 2. Each circuit gets its own 15 A time-delay fuse or HACR breaker. If the second circuit can't supply enough power, the primary stage keeps running, so the RV still has cooling or heating at reduced capacity.

Can I run the system on a 30 A shore connection?
Yes, but you may have to limit what runs at the same time. On RVs designed for a 50 A cord, when only 30 A is available you will usually need to turn off one air conditioner or stage to avoid tripping the main breaker. Use the zone or stage selection to switch off the load you don't need.

Do I need a remote temperature sensor?
No, it's optional on a single-zone installation, because the Comfort Control Center can sense the room temperature itself. A remote sensor is useful when the control has to sit somewhere that isn't representative of the room. If you use one, plug it into P4 (white). Mount it 54 inches above the floor on an inside partition, away from sun, lamps, outside doors and supply registers.

What kind of signal does the load shed input need?
The load shed input needs a normally open relay contact from your energy management system. When the EMS wants the compressor off, the contact closes across the two YEL load shed wires at P6 on CB1. Never feed voltage into these wires. They expect a dry contact closure only. If you don't have an EMS, leave the input unconnected.

Can I connect the furnace blower relays to any furnace?
Not necessarily. The FB1 and FB2 relays run the furnace blower along with the compressor to improve air circulation, but the circuit does not work with every furnace. Some furnaces need extra components. Check the furnace manufacturer's instructions for the correct connection before you wire the BLK field wire. Also install a damper at the furnace outlet unless the furnace is designed to share its blower this way.

What DC voltage does the control system need?
The Comfort Control Center and boards need 10 to 30 V DC. A normal 12 V RV battery or converter supply works. Above 30 V you risk damaging components, and outside the range the system can act erratically. A converter with heavy AC ripple can push the board's filtered voltage higher, so measure at the board end as well as at the source.

Why does the compressor wait before starting?
The control has a built-in delay of about 2 minutes every time the compressor is called for cooling or heat pump operation. This protects the compressor from short cycling. On dual units, circuit 2 is the second stage. It starts after circuit 1, and only when the room is past the primary setpoint by your differential (0 to 10°F).

What does the ambient sensor do on the heat pump?
The ambient sensor reads the outdoor temperature and is used only on heat pumps. It lets the heat pump run down to 24°F and controls defrost between 24°F and 42°F. Below 24°F the control switches to the furnace. If there's no furnace, the system shuts down until the outdoor temperature rises above 34°F. On the 39424, each board needs its own ambient sensor in P3 (red).

Related Product Diagrams

Go up