Generac 200 AMP Automatic Transfer Switch Wiring Diagram

Generac 200 AMP Automatic Transfer Switch Wiring Diagram

Generac 200 AMP Automatic Transfer Switch Wiring Diagram

5/5 (1👤)
💡 Home Electrical 🧮 2 schematics
★Rate It★

How many stars do you give this diagram?

Interconnections

Utility, generator, transfer switch and panel, with the power and control leads.

Interconnections
UTILITY SUPPLY FROMSERVICE DISCONNECTQT SERIES GENERATOR CONNECTION PANELRTS TRANSFER SWITCHCUSTOMER LOAD(DISTRIBUTION PANEL)NOTE: POWER AND CONTROLIN DIFFERENT CONDUITSCOIL C1(UTILITY)COIL C2(STANDBY)TRANSFERCONTACTORTB15 1836 178178 AND 183: NOT USEDTB STRIP3N1N2E1E2ONE1E2T1T2NEUTRALNBGROUND1 N12 N2123 234 19445

Terminals and components · 7

  • Utility (N1, N2)
  • Generator (E1, E2)
  • Load (T1, T2)
  • Neutral
  • Ground
  • Utility sensing
  • Control 23 / 194

About This Diagram

These diagrams are redrawn from pages 11–13 of the Generac 200 AMP Automatic Transfer Switch manual, and we offer them completely free and in English. We have also categorized it in the Generators & Transfer Switches (Home Electrical) section on Diagramverse, and it has been rated by 1 user with an average rating of 5.0. If you have any specific questions about the Generac 200 AMP Automatic Transfer Switch Wiring Diagram, we suggest checking the Frequently Asked Questions (FAQs) section.

Printable Generac 200 AMP Wiring Diagrams

Complete

1 / 2
Generac 200 AMP Automatic Transfer Switch Wiring Diagram – Complete
Generac 200 AMP Automatic Transfer Switch Wiring Diagram – TB strip

Wiring Instructions

Before you start

The Generac 200 AMP switch carries service-level current and connects to the utility supply. In most areas the job needs a permit and an inspection, and a licensed electrician should do the work or check it. Use the Complete tab to plan the power, neutral, ground and control runs. Use the TB strip tab when you land the control wires on terminals TB-1 to TB-5.

  • Tools: torque wrench, wire brush, insulated hand tools, an accurate AC voltmeter and a frequency meter.
  • Power conductors: the 200 A lugs accept #6 to 250 MCM. Size the conductors for the load using the 75°C column of the ampacity tables. If you use aluminum conductors, apply corrosion inhibitor to them.
  • Control wires (N1, N2, 23 and 194): use No. 18 AWG up to 460 feet, No. 16 AWG up to 730 feet, No. 14 AWG up to 1,160 feet and No. 12 AWG up to 1,850 feet.
  • Mounting: mount the NEMA 3R enclosure vertically on a rigid, level surface, as close as practical to the loads. If you need to level it, put washers behind the mounting holes. The knockouts take 1, 1-1/2 and 2 inch conduit.

Before you touch anything, isolate everything:

  • Set the generator AUTO-OFF-MANUAL switch to OFF and remove the generator's negative battery cable.
  • Open the generator main breaker and the utility service disconnect.
  • Tag both the generator and the switch "DO NOT OPERATE".
  • Confirm with your meter that N1, N2, E1 and E2 read zero volts.

Step-by-step wiring

  1. Check the handle position. With the handle UP, T1 and T2 are connected to N1 and N2 (utility). With the handle DOWN, they are connected to E1 and E2 (generator). Leave it UP.
  2. Bring all power cables into the enclosure next to the transfer mechanism terminals. Strip each conductor and wire-brush the surface oxides off the ends.
  3. Land the two utility hot leads from the service disconnect on N1 and N2.
  4. Land the generator hot leads from the generator main breaker on E1 and E2.
  5. Land the distribution panel hot leads on T1 and T2.
  6. Connect the generator neutral and the panel neutral to the Neutral block (NB). This 2-pole mechanism never switches the neutral.
  7. Connect the equipment grounding conductor to the Ground lug (GND) and run it to the distribution panel as your electrical code requires.
  8. Torque every power lug to the value on the decal inside the door, which is 275 in-lbs for the 200 A switch. Overtightening damages the switch base, and a loose lug overheats. Wipe away any excess inhibitor.
  9. Check that there is at least 1/2 inch of clearance between live metal and grounded metal.
  10. Run the control cable to the generator. Connect TB-1 (Utility 1, N1) to generator TB1-1 and TB-2 (Utility 2, N2) to generator TB1-2.
  11. Connect TB-4 to generator terminal 23 (wire 23) and TB-5 to generator terminal 194 (wire 194). Keep the wire numbers the same at both ends.
  12. If you have a prepackaged standby generator, leave TB-3 (Neutral, optional) unused.

Testing and start-up

Have the installation inspected before you test it, and run these tests in this order.

  1. Manual check: with both sources off, insert the handle, move it DOWN, then move it back UP. Hold the handle firmly, because it snaps over once it passes center.
  2. Utility voltage: close the utility disconnect and measure N1 to N2, N1 to neutral and N2 to neutral. Confirm the voltage is correct and within the switch rating, then open the disconnect again.
  3. Generator voltage: set the generator to MANUAL and let it warm up at no load for at least five minutes. Close its main breaker CB1 and measure. You should see 60 to 62 Hz, 240 to 246 VAC across E1 and E2, and 120 to 123 VAC from E1 to neutral and from E2 to neutral. Then open CB1 and set the generator to OFF. Do not continue until these readings are correct.
  4. Load test: with CB1 open, move the handle DOWN. Start the generator in MANUAL, close CB1 and apply loads up to the generator's rated capacity. Across E1 and E2 you should read more than 230 V and more than 59 Hz. Run it for at least 30 minutes and watch for noise, vibration or overheating.
  5. Restore: open CB1, let the generator run at no load for a few minutes, then set it to OFF. Move the handle UP, close the utility disconnect and set the generator to AUTO.

Safety notes

  • The voltages inside the enclosure are lethal. N1, N2, TB-1 and TB-2 stay live whenever utility power is on, even if the generator is off.
  • In automatic mode the generator can crank and start without warning. Disable it before you work on the switch.
  • Never transfer manually under load, and never jumper or bypass the switch. Its job is to keep the generator from backfeeding the utility lines.
  • The 200 A switch is for optional standby systems only. It is rated for circuits up to 10,000 rms symmetrical amperes at 240 VAC. Keep the tungsten (incandescent) load at or below 30% of the switch rating.
  • Remove jewelry before working. When you finish, put the handle back in its storage position and keep the door closed and bolted.

Troubleshooting

Symptom Probable Cause What to Check
Generator starts and runs even though utility power is on The generator isn't seeing utility voltage: a TB-1 or TB-2 sensing wire is open or loose, or fuse F1 or F2 has blown With utility on, measure between TB-1 and TB-2. You should read the same voltage as across N1 and N2. If you don't, check fuses F1 and F2 and the wires to generator TB1-1 and TB1-2.
Generator does not start when the power goes out Sensing wires landed on the wrong generator terminals, or the generator isn't in AUTO Confirm that TB-1 goes to generator TB1-1 and TB-2 goes to TB1-2, and that the AUTO-OFF-MANUAL switch is set to AUTO
Generator runs during an outage but the house stays dark Wire 23 or 194 is missing, loose or swapped, so relay TR never energizes Check that wire 23 goes from generator terminal 23 to TB-4 and wire 194 goes from terminal 194 to TB-5. Check continuity of each wire end to end.
The 5 A fuses keep blowing Short or nicked insulation in the sensing wiring, or a sensing wire touching neutral or ground With power off, check TB-1 and TB-2 for shorts to each other, to TB-3 and to ground. Replace the fuses only with 5 A fuses.
On generator power, lights flicker or 120 V devices get too much or too little voltage Open or loose neutral between the generator and the neutral block Tighten the generator neutral at NB. E1 to neutral and E2 to neutral should each read 120 to 123 VAC at no load.
A power lug or cable insulation looks scorched or feels hot Undertorqued lug, oxidized conductor ends, or aluminum wire without corrosion inhibitor With power off, clean the conductor, apply inhibitor if it is aluminum, and torque to 275 in-lbs or the value on the door decal
Panel is dead on utility power even though the meter shows utility present Handle left in the DOWN (generator) position, or utility cables landed on E1 and E2 instead of N1 and N2 With power off, check the handle position (UP means utility) and confirm that utility feeds N1 and N2, the generator feeds E1 and E2, and the panel is on T1 and T2
Voltage sags badly when large loads start on generator Generator overloaded or power conductors undersized for the run Under rated load, E1 to E2 should stay above 230 V and the frequency above 59 Hz. Recheck conductor size against the 75°C ampacity column.
Correct voltage at no load but the frequency is wrong, or the other way round Generator setting issue, not switch wiring If the frequency is outside 60 to 62 Hz, the engine governed speed needs adjustment. If only the voltage is outside 240 to 246 VAC, the voltage regulator needs adjustment.
Transfer is erratic on a long run between the switch and the generator Control wires undersized for the distance Compare the wire gauge with the run length: No. 18 AWG up to 460 feet, No. 16 up to 730 feet, No. 14 up to 1,160 feet, No. 12 up to 1,850 feet
You feel a tingle when you touch the enclosure Ground lug not connected, or a hot conductor touching the enclosure Shut off both sources, check the GND conductor back to the panel, and check the 1/2 inch clearance around the live lugs

Frequently Asked Questions (FAQs)


Which diagram tab should I use for my installation?
Use both, because they show the same switch at two levels of detail. The Complete tab shows how the utility, generator, load panel, neutral block, ground and control wiring connect to each other, so start there to plan your runs. The TB strip tab zooms in on the customer terminal strip, TB-1 to TB-5, and shows the fuse and relay each terminal goes through. Keep it open while you land the control wires that go to the generator.

What size wire do the 200 A power lugs accept?
The 200 A lugs accept conductors from #6 AWG up to 250 MCM, copper or aluminum. Size the conductors for the maximum current they will carry using the 75°C column of the ampacity tables, and follow your local code. Torque the lugs to 275 in-lbs, or to the value on the decal inside the door. If you use aluminum, clean the ends and apply corrosion inhibitor before you tighten.

Does this transfer switch switch the neutral?
No. This is a 2-pole mechanism that switches only the two hot legs. The utility, generator and panel neutrals stay solidly connected through the neutral block. That design is for single-phase 120/240 V systems where the neutral is not switched. If your installation needs a switched neutral, this switch is not the right choice, so have an electrician confirm what your system requires before you buy.

Do I need to connect the optional neutral terminal TB-3?
Not with a prepackaged standby generator. TB-3 is tied to the neutral block, but those generators don't use it, so you can leave it empty. Use it only if your generator's interconnection instructions specifically call for a neutral at the control strip. The required control connections are TB-1, TB-2, TB-4 and TB-5.

What do the 5 A fuses F1 and F2 protect?
They protect the utility sensing circuit. F1 sits between utility lug N1 and TB-1, and F2 sits between N2 and TB-2. The sensing wires carry utility voltage to the generator so it can detect an outage. A short in that small wiring blows a fuse instead of damaging the wire or the generator controller. If you replace one, use a 5 A fuse.

Can I install this switch outdoors?
Yes. The standard enclosure is NEMA 3R, which protects against falling rain and sleet and isn't damaged by ice forming on it. Mount it vertically on a rigid, level structure, use outdoor-rated conduit fittings in the knockouts, and keep the door closed and bolted. Mount it as close to the loads as practical so the conductor runs stay short.

Can I transfer the switch by hand during an outage?
Only with both sources turned off. The switch must never be moved by hand under load. Open the utility disconnect and the generator main breaker, set the generator to OFF, then use the supplied handle. UP is utility and DOWN is generator. The handle snaps once it passes center, so hold it firmly. Return the handle to its storage position afterward.

What kinds of loads can this switch feed?
It can feed motors, electric discharge lamps such as fluorescent fixtures, tungsten filament lighting and electric heating equipment. The one limit is that tungsten (incandescent) load must not exceed 30% of the switch rating. The switch is listed only for optional standby systems, not for emergency or legally required standby systems. Also check that the total load fits your generator's capacity.

Can I use this switch with a generator from another brand or a portable generator?
Only if the generator has a matching control interface. The switch has no controller of its own. The generator senses utility voltage through TB-1 and TB-2 and drives relay TR through wires 23 and 194. A generator without those connections can't operate the switch automatically. If you are unsure, check the generator's documentation or ask the dealer before you buy or wire it.

Related Product Diagrams

Go up