Honeywell T5 Smart Thermostat Wiring Diagram

Honeywell T5 Smart Thermostat Wiring Diagram

Honeywell T5 Smart Thermostat Wiring Diagram

5/5 (1👤)
🌡️ HVAC & Water Heating 🧮 16 schematics
★Rate It★

How many stars do you give this diagram?

Heat only

Forced-air furnace: gas, oil, electric or fan coil.

Heat only
Heat onlyWiring between the UWP wall plate and the equipmentT5 THERMOSTATUWP PLATEFORCED-AIR FURNACEGas or oilFORCED-AIR FURNACEElectric or fan coilFORCED-AIR FURNACETwo-stageR SWITCH ↑ · 1 WIRERR24 V AC from transformerCCTransformer commonWWHeat · stage 1W2W2W2Heat · stage 2GGGIndoor fan~

Terminals and components · 4

  • R · 24 V
  • Common
  • Heat

About This Diagram

These diagrams are redrawn from the Honeywell T5 Smart Thermostat manual, and we offer them completely free and in English. We have also categorized it in the Thermostats (HVAC & Water Heating) section on Diagramverse, and it has been rated by 1 user with an average rating of 5.0. If you have any specific questions about the Honeywell T5 Smart Thermostat Wiring Diagram, we suggest checking the Frequently Asked Questions (FAQs) section.

Printable Honeywell T5 Wiring Diagrams

Heat only · 1 stage

1 / 16
Honeywell T5 Smart Thermostat Wiring Diagram – Heat only · 1 stage
Honeywell T5 Smart Thermostat Wiring Diagram – Heat only · 1 stage + fan
Honeywell T5 Smart Thermostat Wiring Diagram – Heat only · 2 stages
Honeywell T5 Smart Thermostat Wiring Diagram – Cool only · 1 stage
Honeywell T5 Smart Thermostat Wiring Diagram – Cool only · 2 stages
Honeywell T5 Smart Thermostat Wiring Diagram – Heating and cooling · 1H/1C
Honeywell T5 Smart Thermostat Wiring Diagram – Heating and cooling · 2H/1C
Honeywell T5 Smart Thermostat Wiring Diagram – Heating and cooling · 1H/2C
Honeywell T5 Smart Thermostat Wiring Diagram – Heating and cooling · 2H/2C
Honeywell T5 Smart Thermostat Wiring Diagram – Heating and cooling · 1H/1C · 2 transf.
Honeywell T5 Smart Thermostat Wiring Diagram – Boiler · Boiler
Honeywell T5 Smart Thermostat Wiring Diagram – Boiler · Zone valve
Honeywell T5 Smart Thermostat Wiring Diagram – Heat pump · 1H/1C
Honeywell T5 Smart Thermostat Wiring Diagram – Heat pump · 2H/1C
Honeywell T5 Smart Thermostat Wiring Diagram – Heat pump · 2H/2C
Honeywell T5 Smart Thermostat Wiring Diagram – Heat pump · 3H/2C

Wiring Instructions

Before you start

You need a small flat-head screwdriver, a Phillips screwdriver, a wire stripper, needle-nose pliers, a pencil, a level and a drill with a 7/32 in bit for the wall anchors. A multimeter that reads AC volts helps you check the 24 V supply. The UWP wall plate comes with anchors and three #8 1-1/2 in screws.

Reuse the existing Honeywell T5 Smart Thermostat  cable if it is in good condition. No wire gauge is specified for this thermostat. Standard 18 AWG solid thermostat cable is the usual choice for 24 V AC control wiring, with one conductor per terminal plus one for C. If no C wire reaches the thermostat, pull a new cable or have an HVAC technician add one before you install the T5.

Turn off power at the breaker or switch that feeds the heating and cooling system. Then change the setpoint on the old thermostat: if nothing starts within 5 minutes, the system is off. Remove the old faceplate. Thick black wires with wire nuts, or a thermostat rated 120 V or higher, mean a line voltage system such as electric baseboard heat, and the T5 will not work on it. It also does not work on millivolt systems. Call a licensed HVAC contractor if you find line voltage, wires on L/A, S or U terminals, or a heat pump with V and VR wires. Swapping a thermostat on existing low-voltage wiring rarely needs a permit, but check local rules before running new cable.

Pick the tab that matches your equipment: Heat only for a furnace without air conditioning, Cool only for air conditioning alone, Heating and cooling for a furnace plus central air, Boiler for a boiler or zone valve, and Heat pump when you have an O/B wire. A W2 or Y2 wire means a second stage. Separate R and Rc wires from two transformers match the 1H/1C · 2 transf. variant.

Step-by-step wiring

  1. Photograph the old wiring, including the letters beside each terminal, and label every wire with its terminal letter, especially if colors are faded or repeated.
  2. Remove any jumper, such as a short wire or metal staple between R and Rc. The T5 does not use jumpers.
  3. Disconnect the wires, remove the old wall plate and wrap the wires around a pencil so they cannot fall back into the wall.
  4. Feed the bundle through the back of the UWP and make sure at least 1/4 in of bare copper is exposed on each conductor.
  5. Level the plate, mark the holes, drill and insert the anchors flush with the wall. Leave the plate loose for now; wiring is easier off the wall.
  6. Set the R switch. With one R, Rh or Rc wire, slide it up and insert that wire in R. With two wires, slide it down, put Rc in Rc and R or Rh in R. If the old thermostat had R and RH, the R wire goes to Rc and the RH wire to R.
  7. Connect the common to C. On conventional systems an old C1, X or B wire is the common.
  8. Connect the remaining wires to matching letters: W and W2 for heat, Y and Y2 for cooling or compressor, G for the fan, plus O/B, AUX and E on heat pumps. Old W1 or H labels go to W, Y1 or M to Y, and F to G. On a heat pump with separate O and B wires, or with Y1, W1 and W2 wires, stop and call a qualified contractor.
  9. Press each terminal tab, insert the wire into the inner hole, one wire per terminal, and release. Tug each wire gently to confirm it holds.
  10. Push excess wire into the wall, mount the UWP with all three screws and close its door. Compare every terminal with your photo, then snap the thermostat firmly onto the plate.

Testing and start-up

Restore power at the breaker or switch. The display should come on; if it stays blank, the C circuit is not complete. Pull the thermostat off the plate and measure AC volts between R and C: you should read about 24 V AC.

Go through the installer setup and set the heating system type, the heating equipment type, the number of cool or compressor stages and heat stages, and, on heat pumps, whether O/B energizes in cool (O) or in heat (B). Wrong settings cause as many start-up complaints as wrong wires.

Test each mode: Heat with the setpoint above room temperature, Cool with it below, then fan On. Allow up to 5 minutes for a response; Heat On or Cool On flashing is compressor protection, not a fault. On a heat pump, confirm warm air in Heat, cool air in Cool, and that Em Heat runs the backup heat without the compressor.

Safety notes

  • The thermostat circuit is 24 V AC, but the furnace, air handler and outdoor unit carry 120 V or 240 V. Keep equipment power off while you work and leave equipment panels to qualified technicians.
  • Never let a bare R wire touch C: the short can blow a low-voltage fuse on the control board, if fitted, or damage the transformer.
  • Never connect the T5 to 120–240 V line voltage heaters or millivolt systems.
  • On two-transformer systems the R switch must be down so the transformers stay separate.
  • If the old thermostat has a sealed mercury tube, do not trash it; ask your local waste authority about recycling.

Troubleshooting

Symptom Probable Cause What to Check
The screen stays blank after I turned the power back on No C wire, C wire loose at the thermostat or equipment, or equipment power still off Remove the thermostat and measure AC volts between R and C on the plate: expect about 24 V AC. If you read 0 V, check the breaker, the equipment power switch, the furnace door and the C connection at the control board.
The thermostat turns on but the furnace or AC never starts Equipment service switch off, furnace door not closed, or compressor delay running Make sure the equipment switch is on and the furnace door is closed securely. Set Heat above or Cool below room temperature and wait 5 minutes before you decide it has failed.
The heat runs nonstop as soon as power is restored A leftover jumper or bare copper touching between R and W Turn off power, take the thermostat off and look for staples, short jumper wires or stray strands across terminals. Trim each wire so only about 1/4 in is bare and sits fully inside the terminal.
My heat pump blows cold air in Heat and warm air in Cool Reversing valve setting does not match the equipment, or O/B wire on the wrong terminal Confirm the O/B wire is on O/B, then change the O/B setting in the installer setup from O (energize in cool) to B (energize in heat), or the reverse.
I cannot select Cool mode Cool or compressor stages set to 0 In the installer setup, set cool stages to 1 or 2 and make sure the Y wire is landed on Y.
Heat works but the AC does nothing on my system with two transformers R switch left up, or the Rc wire missing or in the wrong terminal Turn off power, set the R switch down, put the cooling transformer wire in Rc and the heating wire in R. Use the 1H/1C · 2 transf. variant.
The fan does not come on when the heat is running Heating equipment type set wrong, or G wire not connected Set the heating equipment type to match your furnace or fan coil, and check the G wire at both the thermostat and the equipment.
The thermostat went dead and the system stopped right after I wired it R shorted to C, blowing the control board fuse or overloading the transformer With power off, check that no R strand touches C. Inspect the low-voltage fuse on the control board, if fitted, and replace it with the same rating. Measure 24 V AC between R and C again.
The second stage never comes on W2 or Y2 not connected, or stages set to 1 Confirm the wire sits in W2 or Y2 and set heat stages or compressor stages to 2 in the installer setup.
Em Heat or auxiliary heat does nothing on my heat pump AUX or E wire missing, or backup heat stages set to 0 Check that the heat strip wire is in AUX or E, and set backup heat stages to 1.
The system works only sometimes or cuts out randomly A wire not fully seated in the push terminal or not stripped enough Press each terminal tab, reinsert the wire into the inner hole with 1/4 in of bare copper, release and give it a gentle tug.

Frequently Asked Questions (FAQs)


How do I wire a Honeywell T5 thermostat?
You wire a Honeywell T5 by moving each labeled wire from the old thermostat to the matching letter on the UWP wall plate. Turn off the HVAC power, photograph and label the wires, and remove any jumpers. Set the R switch up for one R wire or down for separate R and Rc wires. Then connect C and the call wires: W, W2, Y, Y2, G, and O/B, AUX and E on heat pumps. Mount the plate, snap the thermostat on, restore power and complete the installer setup.

Does the Honeywell T5 require a C wire?
Yes, the T5 needs a C wire. The common wire is the return side of the 24 V AC transformer, and the T5 draws its operating power through R and C continuously. Without a C wire the display will not stay on. If your cable has a spare conductor, connect it to C at the thermostat and to the common terminal on the equipment control board. If no spare conductor exists, run new thermostat cable or have an HVAC technician add a common.

Can I use the T5 with electric baseboard heaters?
No, the T5 cannot control electric baseboard heat or any other 120–240 V line voltage heater. It is a 24 V AC low-voltage thermostat. Line voltage systems usually have thick black wires joined with wire nuts at the old thermostat, which is marked 120 V or higher. The T5 also does not work with millivolt systems, such as some gas fireplaces and wall furnaces. Use a thermostat rated for line voltage or millivolt operation instead.

What does the R switch on the wall plate do?
The R switch tells the plate whether R and Rc are joined or kept separate. In the up position it links R and Rc inside the plate, which is right for single-transformer systems with only one R, Rh or Rc wire. In the down position it separates them, so a heating transformer on R and a cooling transformer on Rc stay isolated. Set it before inserting the wires, and check it again if one mode does not respond.

Do I need to keep the jumper between R and Rc from my old thermostat?
No, discard the jumper. The T5 does not use jumpers between terminals. The function of the old R to Rc jumper is handled by the R switch: up joins R and Rc inside the plate, so a single R wire powers both heating and cooling. Leaving a metal staple or short wire in place is unnecessary and could short terminals together. Do not count jumpers as wires when you choose the R switch position.

Does the T5 work with a heat pump?
Yes, the T5 controls air-to-air heat pumps with up to two compressor stages, one auxiliary heat stage and emergency heat. Wire the reversing valve to O/B, the compressor to Y and Y2, heat strips to AUX and emergency heat to E. Then set whether the valve energizes in cool (O) or heat (B). Keep the R switch up. A heat pump with separate O and B wires or V and VR wires needs a contractor's help.

Can the T5 control a boiler or a zone valve?
Yes, the T5 can control a boiler or a 24 V zone valve through the W terminal, with R and C for power. For a boiler, W sends the call for heat. For a zone valve, the valve motor sits between W and C. Choose the Boiler tab and the matching variant. In the installer setup, pick radiant heat with hot water or steam so the thermostat cycles correctly for that equipment.

How many heating and cooling stages can the T5 handle?
On conventional systems the T5 controls up to two heat stages on W and W2 and up to two cooling stages on Y and Y2. On heat pumps it handles up to two compressor stages plus one auxiliary or emergency heat stage, which is the 3H/2C variant. Tell the thermostat how many stages you have in the installer setup. Equipment with more stages than these needs a different control.

Can I reuse my existing thermostat wire?
Yes, you can reuse the existing cable if it has enough conductors, including one for C, and the insulation and copper are in good shape. Cut back any nicked or corroded ends and strip fresh copper, leaving about 1/4 in bare. No gauge is specified for the T5, so check your equipment instructions. Standard 18 AWG solid thermostat cable is the common choice when you replace it or add a C wire.

Which diagram tab should I use for a furnace with central air?
Use the Heating and cooling tab, then pick the variant by counting stages. One W and one Y wire is 1H/1C. A W2 wire adds a heat stage, giving 2H/1C, and a Y2 wire adds a cooling stage, giving 1H/2C. Both together is 2H/2C. If the furnace and air conditioner each have their own transformer, with separate R and Rc wires, choose 1H/1C · 2 transf. and set the R switch down.