Danfoss TP5000SI Thermostat Wiring Diagram

Danfoss TP5000SI Thermostat Wiring Diagram

Danfoss TP5000SI Thermostat Wiring Diagram

5/5 (1👤)
🌡️ HVAC & Water Heating 🧮 7 schematics
★Rate It★

How many stars do you give this diagram?

Danfoss TP5000 Si thermostat wiring

Output relay 1-2-3, power supply (batteries or 230 V) and S1/D-S2/E remote input.

Danfoss TP5000 Si thermostat wiring
THERMOSTATELECTRONICSRELAYHEATING LOADboiler or valveREMOTE INPUTsensor or contact230 V AC MAINS50 Hz1NCOFF2COM3NOON2 × AA cellsBNCLS1DS2ETP5000A Si onlyTP5000MA Si only

Terminals and components · 5

  • COM
  • NO / ON
  • NC / OFF
  • Batteries
  • Remote input

About This Diagram

These diagrams are redrawn from page 4 of the Danfoss TP5000SI Thermostat Data Sheet, and we offer them completely free and in English. We have also categorized it in the Thermostats (HVAC & Water Heating) section on Diagramverse, and it has been rated by 1 user with an average rating of 5.0. If you have any specific questions about the Danfoss TP5000SI Thermostat Wiring Diagram, we suggest checking the Frequently Asked Questions (FAQs) section.

Printable Danfoss TP5000SI Wiring Diagrams

Complete · TP5000 Si / A Si (battery)

1 / 7
Danfoss TP5000SI Thermostat Wiring Diagram – Complete · TP5000 Si / A Si (battery)
Danfoss TP5000SI Thermostat Wiring Diagram – Complete · TP5000M Si / MA Si (230 V)
Danfoss TP5000SI Thermostat Wiring Diagram – Remote inputs · Remote or limit sensor
Danfoss TP5000SI Thermostat Wiring Diagram – Remote inputs · One contact
Danfoss TP5000SI Thermostat Wiring Diagram – Remote inputs · Window and teleswitch
Danfoss TP5000SI Thermostat Wiring Diagram – RX receivers · RX1
Danfoss TP5000SI Thermostat Wiring Diagram – RX receivers · RX2 / RX3

Wiring Instructions

Before you start

First, find out which model you have, because this tells you which diagram view to follow. The Danfoss TP5000SI and TP5000A Si run on two AA alkaline cells and need no mains supply. The TP5000M Si and TP5000MA Si run on 230 V, 50 Hz mains. Models with an "A" in the name have the S1/D · S2/E remote input. The RF models are wireless: the thermostat holds no load wiring, and the load connects to an RX1, RX2 or RX3 receiver instead. Pick the matching variant in the Complete, Remote inputs or RX receivers tab before you begin.

This product should be installed by a qualified electrician or competent heating installer, following your local wiring regulations. Have these ready:

  • Small flat and Phillips screwdrivers, wire strippers and a non-contact voltage tester
  • A multimeter with continuity and AC voltage ranges
  • Two high-quality AA alkaline cells for battery models
  • Cable suited to mains voltage for the relay and supply circuits. The sources give no conductor size, so size the cable to the circuit protection and to local code. The relay is rated 3(1) A, 10–230 V, so it is a control-circuit device, not a direct heater switch.

Turn off the circuit that feeds the boiler, valve or heating controls at the breaker or fused spur. Lock it off if you can, and use your tester to confirm the conductors are dead. Many heating circuits are fed from more than one source, so test every conductor in the back box.

Step-by-step wiring

  1. Remove the wallplate from the back of the unit. Check the mounting position: about 1.5 m above the floor, away from draughts, radiators, open fires and direct sunlight. Measured from the top left corner of the wallplate, leave at least 15 mm clear to the left and right, 30 mm above and 100 mm below. The plug-in module needs that space.
  2. Set the 8 DIL switches on the rear of the unit before mounting. They select the number of events, 5/2 day or 24 hour, chrono-proportional or on/off control, keyboard lock and reset. Record any changes you make from the factory positions.
  3. Deal with old neutral and earth wires (battery models). If the old thermostat had a neutral or earth wire, do not connect it to any TP5000 Si terminal. Insulate each one safely and coil it into the recess at the back of the unit.
  4. Connect the supply (230 V models only). Land the live on C / L and the neutral on B / N, and connect the protective earth to the ⏚ terminal. This supply powers only the thermostat's electronics.
  5. Wire the relay. Bring the supply for the heating load circuit to 2 · COM. Connect the boiler or valve "call for heat" conductor to 3 · NO, which closes on heat demand. Use 1 · NC only if your equipment needs a signal while there is no demand. The contact is voltage free, so the same relay can switch a low-voltage boiler input or a 230 V valve circuit, as long as you stay within 10–230 V and 3(1) A.
  6. Wire the remote input (A and MA models). The terminal block sits on the circuit board above the battery compartment. Connect a TS2 remote room sensor or a floor limit sensor across S1/D and S2/E. If you are using one voltage-free contact, connect it across the same pair. For a window contact plus a teleswitch, wire both NC contacts in series across the two terminals.
  7. Wire the RX receiver (RF models). Give the receiver a permanent 230 V supply that is never switched by a timeswitch. On mains-voltage systems, link terminal 2 (COM) to the live. Then connect zone 1 to terminal 3, zone 2 to 5 (RX2 and RX3) and zone 3 to 6 (RX3 only).
  8. Dress the cables neatly, check every screw terminal with a light tug, and refit the unit to the wallplate.

Testing and start-up

  • On battery models, fit the cells with the polarity marked inside the battery compartment. Then press and release RESET. The display may stay blank until you do this. Press RESET on 230 V models too, before any commissioning or programming.
  • Before you restore power, use the multimeter's continuity range to test the relay. Turn the setpoint up to call for heat: 2–3 should read closed and 2–1 open. Turn it down and the readings should swap.
  • Restore power. Raise the setpoint and confirm the boiler or valve starts, then lower it and confirm it stops.
  • If you fitted a remote input, open Installer Advanced Programming and set option 90:
    • 0: no remote sensor
    • 1: remote room or duct sensor (the built-in sensor is then disabled)
    • 2: limit sensor. Set the limit with option 93 (20–50°C).
    • 3: digital input. Use option 94 to choose NC (0) or NO (1).
  • To pair an RF model, press RESET on the thermostat, then hold V and + for 3 seconds. On the RX1, hold PROG and CH1 until the green light flashes once. Use CH2 and CH3 for the extra thermostats on an RX2 or RX3. A thermostat and RX1 sold in a combined pack come paired from the factory.

Safety notes

  • Even on a battery thermostat, the relay terminals can carry 230 V from the heating circuit. Treat them as live until you have proved them dead.
  • Don't exceed the 3(1) A rating: 3 A resistive, 1 A inductive. Switch pumps, large valves or electric heating through a suitably rated contactor or relay.
  • The S1/D and S2/E input takes only a sensor or a voltage-free contact. Never connect mains to it.
  • In buildings at risk of freezing, set option 38 so the relay is held ON when the batteries run out. Keep the RF thermostat within 30 m of the receiver, with no boiler cases or large metal objects in the line between them.

Troubleshooting

Symptom Probable Cause What to Check
The display stays blank after I fitted the batteries Batteries in the wrong way round, or the unit hasn't been reset Check each cell against the polarity marks in the compartment, fit fresh alkaline cells and press and release RESET. Don't leave batteries in a unit whose display won't come on.
The thermostat shows a demand but the boiler never fires No supply on 2 · COM, or the load is wired to 1 · NC instead of 3 · NO With power off, measure continuity: 2–3 should close on demand. With power on, confirm the load supply is on COM and that the boiler conductor is on terminal 3.
The heating runs when it should be off and stops when it should be on Load connected to 1 · NC Move the load conductor from terminal 1 to terminal 3 and test again by raising and lowering the setpoint.
A breaker trips or something sparks when I connect the old wires An old neutral or earth wire landed on a battery-model terminal Remove the neutral and earth from the TP5000 Si terminals, insulate them and coil them in the rear recess. Only the relay terminals should carry wiring.
The 230 V model won't power up Supply on the wrong terminals or no permanent mains Measure about 230 V AC between C / L and B / N. Check the spur fuse or breaker and make sure the earth is on the ⏚ terminal, not on N.
The room temperature reading is wrong or doesn't change after I fitted a remote sensor Option 90 doesn't match the sensor, or the sensor wiring is loose Set option 90 to 1 for a room sensor or 2 for a limit sensor. Retighten both conductors at S1/D and S2/E.
The display flashes F10 and the floor heating stops The limit sensor has reached the option 93 setpoint, or the setpoint is too low Check the option 93 value (20–50°C). The output comes back once the floor is 2°C below the limit. Check that the sensor is fixed in the right place.
The unit stays in thermostat mode even when the window is closed Option 94 doesn't match the contact type, or the series NC loop is broken Set option 94 to 0 for NC contacts or 1 for NO. Check continuity across S1/D–S2/E with the window closed and the teleswitch in its normal state.
The RF receiver never switches the boiler No live link to terminal 2, a switched receiver supply, or the thermostat isn't paired Confirm a permanent 230 V on the receiver's live and neutral terminals, and the link to terminal 2 on mains systems. Repeat pairing until the green light flashes once.
Zone 2 or zone 3 doesn't respond on a multi-zone receiver Load on the wrong terminal, or the thermostat is paired to the wrong channel Zone 2 is terminal 5 and zone 3 is 6 (RX3 only). Pair each thermostat using PROG with CH2 or CH3.

Frequently Asked Questions (FAQs)


Does the TP5000 Si need a neutral or earth wire?
No, the battery TP5000 Si and TP5000A Si don't use a neutral or earth. They run on two AA alkaline cells and only the relay terminals are wired. If the old thermostat had a neutral or earth, insulate it and coil it in the recess behind the unit. The TP5000M Si and TP5000MA Si are different: they need 230 V live and neutral on C / L and B / N, and the protective earth goes to the earth terminal.

Which TP5000 Si model has the remote sensor input?
Only the models with an "A" in the name have it. That means the TP5000A Si (battery), the TP5000MA Si (230 V) and the wireless TP5000ARF Si. The input is the S1/D and S2/E terminal pair, on the circuit board above the battery compartment. It accepts a remote room sensor, a floor limit sensor, or voltage-free contacts such as a window contact, card reader or teleswitch. On the TP5000 Si and TP5000M Si there is nothing to wire here.

Can the TP5000 Si switch a 24 V boiler input as well as a 230 V circuit?
Yes. The output relay is a voltage-free SPDT contact rated 3(1) A at 10–230 V, so it can switch low-voltage or mains control circuits. Whatever voltage you bring to COM is what appears on NO when there is demand. Check that the boiler's thermostat input is designed for a voltage-free contact, and never mix two different supplies on the same relay.

Can I wire an electric heater directly to the thermostat relay?
Only small loads within the relay rating. The contact is rated 3(1) A: 3 A resistive and 1 A inductive. Most electric heaters, underfloor heating mats and pumps draw more than that, especially at start-up. Use the thermostat to drive the coil of a suitably rated contactor or relay, and let that device switch the heater. Check the current on the heater's rating label before you decide.

What is the difference between a remote room sensor and a limit sensor?
A remote room sensor takes over temperature control, and a limit sensor only protects against overheating. With option 90 set to 1, the remote room or duct sensor (TS2) replaces the built-in sensor, which is useful when the thermostat has to be mounted somewhere unrepresentative. With option 90 set to 2, the built-in sensor still controls the room, and the limit sensor, usually in a floor, cuts the output above the option 93 setpoint.

Can I use a window contact and a teleswitch at the same time?
Yes, as long as both are normally closed contacts wired in series across S1/D and S2/E. Set option 90 to 3 and option 94 to 0, so that opening either contact switches the unit into thermostat mode. Set the temperature it should hold in that mode with user option 10 beforehand. Pressing the two temperature arrow buttons together overrides the input locally.

Should I choose on/off or chrono-proportional control?
Chrono-proportional control usually holds the room temperature more steadily, while on/off is the simpler choice when the heat source shouldn't cycle often. You choose with DIL switch 5. Chrono-proportional mode cycles the output 3, 6, 9 or 12 times per hour (option 34, factory setting 6). On/off mode switches with a ±1°C differential. Confirm with the boiler or heat source manufacturer which mode suits their appliance before you choose.

What happens to the heating when the batteries run out?
The heating turns off unless you set the thermostat otherwise. When the battery symbol appears, there are 15 days to replace the cells before the unit shuts down. Option 38 decides where the relay is parked at shutdown: off (0, factory setting) or on (1). In buildings that could freeze, setting it to on keeps the heating running, at the cost of extra fuel.

Why can't the RX receiver be powered through a timeswitch?
The receiver has to be powered all the time so it can always receive the thermostat's signal and act on it. If a timeswitch cuts its 230 V supply, the receiver loses that link and the zone outputs drop out. Feed it from a permanent supply. If you want timed operation, use the thermostat's own programming.

How far can the wireless thermostat be from its receiver?
The maximum is 30 m, at 433.92 MHz. Walls and especially metal objects reduce that range. Avoid boiler cases or other large appliances in the line between the thermostat and the receiver, because they can block communication completely. Find a good location for the thermostat before fixing it permanently: pair the units first, then test switching from the intended spot.

Related Product Diagrams

Go up