Drayton RTS4 Thermostat Wiring Diagram

Drayton RTS4 Thermostat Wiring Diagram

Drayton RTS4 Thermostat Wiring Diagram

5/5 (1👤)
🌡️ HVAC & Water Heating 🧮 2 schematics
★Rate It★

How many stars do you give this diagram?

Drayton RTS4 thermostat wiring

Wall plate with the 230 V supply and the changeover contact; choose how the common is fed.

Drayton RTS4 thermostat wiring
RTS4 THERMOSTAT · WALL PLATEINTERNAL RELAYSPDT changeover contact230 V AC SUPPLY3 A fuseN3 AL1COML–1 link3 AEXTERNAL CIRCUIT3 A fuse2Heating satisfied orcall for cooling3Call for heat230 V livevoltage from terminal 1earth loop

Terminals and components · 7

  • Live
  • Neutral
  • Common (COM)
  • Call for heat
  • Heating satisfied / cooling
  • Earth loop

About This Diagram

This diagram is redrawn from page 4 of the Drayton RTS4 Thermostat Technical Specifications, and we offer it completely free and in English. We have also categorized it in the Thermostats (HVAC & Water Heating) section on Diagramverse, and it has been rated by 1 user with an average rating of 5.0. If you have any specific questions about the Drayton RTS4 Thermostat Wiring Diagram, we suggest checking the Frequently Asked Questions (FAQs) section.

Printable Drayton RTS4 Wiring Diagrams

L–1 link (230 V)

1 / 2
Drayton RTS4 Thermostat Wiring Diagram – L–1 link (230 V)
Drayton RTS4 Thermostat Wiring Diagram – Volt-free

Wiring Instructions

Before you start

The Drayton RTS4 is an electronic room thermostat with a relay output. It has a single-pole double-throw (SPDT) contact, and that contact is volt-free. Terminals N and L power the electronics. Terminals 1 (COM), 2 (heating satisfied or call for cooling) and 3 (call for heat) form the switch. The switch carries no voltage of its own, so you have to feed terminal 1 in one of two ways. The two diagram variants show each one:

  • L–1 link (230 V): use this when the boiler, zone valve or pump expects a 230 V switched live on its thermostat input. A link from L to 1 means terminal 3 delivers 230 V on a call for heat. Most 230 V system and conventional boiler controls are wired this way.
  • Volt-free: use this when the appliance supplies its own circuit to the thermostat and only needs a contact closure across two terminals, as many combi boilers do. You leave the link out. The appliance's circuit goes to terminal 1 and comes back from terminal 3, and that external circuit must also be protected by a 3 A fuse.

Tools: insulated screwdrivers, wire strippers, pliers for the cable entry strip, a drill with wall plugs, a voltage tester and a multimeter with a continuity range. For fixing you need No 6 x 1" woodscrews for a flat wall, or M3.5 x 14 screws for a flush single conduit box.

The unit is for fixed wiring only and must be installed to current IET wiring regulations (BS7671). The fixed wiring must include a double-pole isolating switch with at least 3 mm contact separation in all poles, and the supply circuit must be fused at 3 A. The documents don't give a cable size. As general practice, use fixed-wiring cable suitable for a 3 A fused circuit, sized and routed to your local wiring regulations. If you aren't competent in mains wiring, or your local rules require notification or certification of the work, have a qualified electrician or heating engineer do the job.

Choose the location before you run cable. Mount the thermostat on an inside wall about 1.5 m (5 ft) above the floor. Keep it out of direct sunlight and drafts, and away from radiators or other appliances that give off heat.

Step-by-step wiring

  1. Switch off and lock off the supply at the isolating switch or consumer unit. With your voltage tester, confirm that no voltage is present on any conductor, including any feed coming from the boiler or wiring center.
  2. If you are replacing an old thermostat, label each wire by function before you disconnect it: live, neutral, call for heat, satisfied and earth. Old ACL and Drayton models use different terminal numbers, so match by function, not by number.
  3. Loosen the securing screws and separate the thermostat from its wall-plate. If you are using surface wiring, snap out the cable entry strip on the bottom edge of the wall-plate with pliers.
  4. Fix the wall-plate with the terminals at the top, either directly to the wall or to the conduit box.
  5. Connect the supply neutral to N. This connection is mandatory. Without it the electronics have no power and the relay never switches.
  6. Connect the 3 A fused live to L.
  7. Feed the common. For the L–1 link (230 V) variant, fit a short insulated link from L to 1. For the Volt-free variant, connect the appliance's thermostat feed wire to 1 and leave out the link.
  8. Connect the appliance's call-for-heat (demand) input to 3.
  9. Use 2 only if you need a signal when heating is satisfied, for example to switch a cooling device or the "closed" side of a valve. Otherwise leave it empty.
  10. If the cable has an earth conductor, terminate it in E so earth continuity carries on through the box. The thermostat itself is double insulated and needs no earth.
  11. Check that each conductor is fully inserted, the screws are tight, no bare copper shows and no strands are loose. Plug the thermostat onto the wall-plate and tighten the securing screws.

Testing and start-up

Before you restore power, confirm that the circuit fuse is 3 A. Switch on and turn the knob well above room temperature. You should hear the relay click, and the appliance should get a call for heat. In the L–1 link variant, terminal 3 should read about 230 V AC to neutral. Turn the knob well below room temperature and the relay should click back. Terminal 3 should then drop to zero, and terminal 2 becomes live through the link.

In the volt-free variant, isolate the external circuit first. Then do the same test with a multimeter on continuity. Terminals 1–3 should be closed on demand and 1–2 closed when satisfied. Finally set the comfort temperature against the setting mark (range 10 to 30 °C). If needed, pull off the knob and reposition the two limiting arms to restrict or lock the setting.

Safety notes

  • Terminals N and L always carry 230 V AC. In the L–1 link variant, terminals 1, 2 and 3 are also at mains voltage.
  • Even in the volt-free variant, the contacts are not SELV. Treat every terminal as mains wiring, and only connect a low-voltage appliance circuit if the appliance's instructions allow it.
  • Always disconnect the mains supply before you fit or remove the thermostat from its wall-plate. A separate external feed on terminal 1 needs its own isolation.
  • Do not exceed the 2(1) A 230 V AC switch rating: 2 A resistive, 1 A inductive. Switch heavier loads such as pumps or large valves through a relay or wiring center.

Troubleshooting

Symptom Probable Cause What to Check
Thermostat never clicks and the boiler never fires No neutral on N, or no 230 V supply on L With power on, measure between L and N. You should see about 230 V AC. If not, check the neutral connection, the 3 A fuse and the isolating switch.
I hear the relay click but the boiler or valve doesn't respond Common not fed: L–1 link missing in a 230 V installation Measure terminal 3 to N on a call for heat. If it reads 0 V where 230 V is needed, fit the link between L and 1, or check the external feed to terminal 1.
Heating runs all the time and the knob makes no difference Demand wire on terminal 2 instead of 3, or the appliance's thermostat input is bridged elsewhere Turn the knob down and confirm that terminal 3 drops to 0 V, or that 1–3 opens on continuity with power isolated. Move the demand wire to 3 and remove any leftover link at the boiler.
Heating comes on when the room is warm and goes off when it's cold Call-for-heat and satisfied wires swapped between 2 and 3 Isolate the supply and check continuity. 1–3 should be closed when set above room temperature, and 1–2 closed when set below. Swap the wires at 2 and 3.
Combi boiler won't respond after fitting the RTS4 in place of an old stat Wrong variant: the boiler's volt-free input wired as 230 V, or the old wiring was transferred by terminal number Check the boiler's thermostat input type. For a volt-free input, remove the L–1 link and wire the boiler loop to 1 and 3. Re-map old ACL or Drayton wires by function.
Fuse blows or the breaker trips when the boiler is called Short circuit from the link or a wire touching another terminal, or a load above the contact rating Inspect for stray strands and a badly placed link. Measure the load current. It must not exceed 2 A resistive or 1 A inductive. Use a relay for larger loads.
Heating works intermittently or cuts out randomly Loose conductor in a terminal, or the thermostat not fully plugged onto the wall-plate Isolate, re-strip and re-tighten every terminal, then refit the thermostat and tighten the securing screws. Recheck the voltage on terminal 3 under demand.
Thermostat switches at the wrong room temperature Poor location: near a radiator, in sunlight, in a draft, or on an outside wall Move it to an inside wall about 1.5 m (5 ft) above the floor, away from heat sources and drafts.
Knob won't turn past a certain point Range limiting arms set under the knob Pull off the knob, lift and rotate the two limiting arms to new notches, then refit the knob at the setting mark.
Earth wire left loose after installation Earth conductor not terminated because the thermostat needs no earth Terminate the circuit earth in terminal E to keep continuity, and check continuity back to the supply earth.

Frequently Asked Questions (FAQs)


Is the Drayton RTS4 a volt-free thermostat?
Yes. The RTS4 has a single-pole double-throw volt-free contact on terminals 1, 2 and 3. The thermostat itself still needs a 230 V AC supply on L and N to run its electronics, but the switch carries no voltage until you feed terminal 1. You can link L to 1 for a 230 V switched output, or bring in a separate circuit protected by a 3 A fuse.

Does the RTS4 need a neutral connection?
Yes, the neutral connection to terminal N is essential. The RTS4 is electronic with a relay output, so without a 230 V supply across L and N the relay will not operate. You will hear no click, and the call-for-heat contact stays open. That's why a simple two-wire mechanical thermostat circuit with no neutral can't drive an RTS4 without adding a neutral conductor.

When should I fit the link between L and terminal 1?
Fit the L–1 link when the appliance needs 230 V on its thermostat input, which is typical of system boilers, wiring centers and zone valves. The link puts the live on the common, so terminal 3 delivers 230 V on a call for heat and terminal 2 delivers 230 V when satisfied. Leave the link out when the appliance supplies its own circuit and only needs a contact closure across 1 and 3.

Can I use the RTS4 with a combi boiler?
Yes, the RTS4 is suitable for combi boilers because of its volt-free contacts. Wire the boiler's thermostat loop to terminals 1 and 3 without the L–1 link, and give the thermostat its own 230 V supply on L and N. The contacts are not SELV, so they are intended for fixed mains-rated wiring. Confirm in the boiler's instructions that its thermostat input is compatible.

Do I need to earth the RTS4?
No, the RTS4 is double insulated and needs no earth. Terminal E is only a loop terminal, provided so you can join the earth conductors of the incoming and outgoing cables and keep earth continuity through the box. If your cable has an earth conductor, terminate it there rather than leaving it loose or cut off.

What fuse rating do I need for the RTS4 supply?
The supply to the RTS4 must be fused at 3 A, at 230 V AC 50 Hz. If you feed terminal 1 from a separate circuit instead of linking from L, that circuit also needs a 3 A fuse. Check the fuse before you switch on for the first time. The fixed wiring must also include a double-pole isolating switch with at least 3 mm contact separation.

How much load can the RTS4 contacts switch?
The contacts are rated 2(1) A at 230 V AC. That means up to 2 A for a resistive load and 1 A for an inductive load such as a motorized valve or pump. That's enough for most boiler thermostat inputs and wiring centers. For anything heavier, let the RTS4 drive a contactor or relay instead of switching the load directly.

What is terminal 2 used for?
Terminal 2 is the "heating satisfied or call for cooling" output. It connects to the common, terminal 1, when the room has reached the set temperature. You can use it to start a cooling device, to drive the closed side of a spring-less valve, or as a satisfied signal for other controls. If your installation only needs a call for heat, leave terminal 2 unused.

Can the RTS4 replace my old ACL or Drayton thermostat?
Yes, the RTS4 can replace earlier ACL and Drayton room thermostats as long as the load doesn't exceed 2(1) A 230 V AC. Terminal numbers differ between models, so transfer the wires by function. On an old Drayton RT or RTE, live was 1, neutral 4 and call for heat 2. On the RTS4 those go to L, N and 3. An old accelerator-heater neutral becomes the required N connection.

Where is the best place to mount the RTS4?
Mount the RTS4 on an inside wall about 1.5 m (5 ft) above the floor, where it senses the true room temperature. Keep it away from direct sunlight, drafts, radiators and other heat-producing appliances, all of which cause false readings. It can be fixed straight to a flat wall or onto a flush single conduit box. Its operating ambient range is 0 to 40 °C.

What temperature range does the RTS4 cover, and can I lock the setting?
The RTS4 controls between 10 and 30 °C. Under the knob there are two limiting arms. You can set them to restrict the dial to a narrower range or lock it at a single setting, which is useful in rented properties, offices or public spaces. Set the temperature first, pull off the knob, reposition the arms in the notches, then refit the knob at the setting mark.

Related Product Diagrams

Go up