EPH Combi Pack 4 Thermostat Wiring Diagram

EPH Combi Pack 4 Thermostat Wiring Diagram

EPH Combi Pack 4 Thermostat Wiring Diagram

5/5 (1👤)
🌡️ HVAC & Water Heating 🧮 1 schematic
★Rate It★

How many stars do you give this diagram?

EPH 4-channel hardwired pack wiring

Each device terminal shows the number of the wiring centre terminal it goes to.

EPH 4-channel hardwired pack wiring
SPUR FUSED @ 3A1N2L3R47Programmer47LNZ1Z2Z3Z4ONONONON1132234556687WRPPipe / cylinder thermostatCOMC4N/O181CM2Room thermostat (1)COM15N/O29CM2Room thermostat (2)COM16N/O210CM2Room thermostat (3)COM17N/O211CAUTION!Consult the boiler installationinstructions before wiring:boiler manufacturers' wiringschematics may vary.HOT WATER VALVE (ZV1)M8BROWN14BLUE12ORANGE13GREY1EARTHHEATING VALVE (ZV2)M9BROWN14BLUE12ORANGE13GREY1EARTHHEATING VALVE (ZV3)M10BROWN14BLUE12ORANGE13GREY1EARTHHEATING VALVE (ZV4)M11BROWN14BLUE12ORANGE13GREY1EARTHWIRING CENTRE12N3L4Z1ONCYLSTATCOM5Z2ONROOMSTAT1COM6Z3ONROOMSTAT2COM7Z4ONROOMSTAT3COM8CYLSTATN/OBROWNCOREZV19ROOMSTAT1N/OBROWNCOREZV210ROOMSTAT2N/OBROWNCOREZV311ROOMSTAT3N/OBROWNCOREZV412ORANGECORE OFVALVES13GREYCORE OFVALVES230V TOBOILER& PUMP14BLUECORE OFVALVESLINK TOTERMINAL3LINK TOTERMINAL2BOILERPUMP1N14L131N14L13

Terminals and components · 13

  • Earth
  • Neutral
  • Live
  • Z1–Z4 ON outputs
  • Valve motor
  • 230 V to boiler and pump

About This Diagram

This diagram is redrawn from page 1 of the EPH Combi Pack 4 Thermostat Wiring Diagram, and we offer it completely free and in English. We have also categorized it in the Thermostats (HVAC & Water Heating) section on Diagramverse, and it has been rated by 1 user with an average rating of 5.0. If you have any specific questions about the EPH Combi Pack 4 Thermostat Wiring Diagram, we suggest checking the Frequently Asked Questions (FAQs) section.

Printable EPH Combi Pack 4 Wiring Diagrams

EPH Combi Pack 4 Thermostat

EPH Combi Pack 4 Thermostat Wiring Diagram

Wiring Instructions

Before you start

This EPH Combi Pack 4 diagram shows the EPH 4-channel hardwired pack (CR4P, CR422P and CR428P). The pack contains an R47 4-channel programmer, a WRP pipe/cylinder thermostat, three CM2 room thermostats, four 2-port motorized valves and a 14-terminal wiring centre. ZV1 is the hot water valve and ZV2 to ZV4 are the heating valves. Some CombiPack4 kits instead come with a battery-powered RFRP-OT thermostat and an RF1A-OT wireless receiver. If that is your kit, this layout does not apply: wire the receiver from its own terminal diagram.

  • Tools: insulated screwdrivers, wire strippers, a multimeter or approved two-pole voltage tester, cable labels and bootlace ferrules for stranded cores.
  • Cable: the sources do not specify a size. Every circuit here carries 230 V, so use mains-rated cable with an earth conductor, sized to your local wiring regulations. Each valve has five cores: brown, blue, orange, grey and earth.
  • Supply: feed the whole system from one 3 A fused spur. The 3 A fuse is the only protective device the system relies on.
  • Isolation: switch off and lock off the spur, take out the fuse and prove the circuit dead before you touch any terminal.
  • Who should do it: this is mains wiring that controls a boiler. Have a qualified electrician or heating engineer do it, and check whether your area requires the work to be notified or certified.

Read the boiler installation instructions before you wire anything. Boiler wiring varies: some boilers need a permanent live supply, some need a pump overrun, and some need a volt-free signal from the valve limit switches instead of the switched live shown on terminal 13. If your boiler needs any of these, its connection will differ from the drawing.

Step-by-step wiring

  1. Mount the wiring centre, the R47 programmer and the thermostats. Put each CM2 about 1.5 metres above the floor, in the zone it controls, away from direct sunlight, radiators and drafts. Fit the WRP to the cylinder as its instructions describe.
  2. Run the supply from the 3 A fused spur to the wiring centre: Earth to 1, N to 2 and L to 3. Keep the spur off.
  3. Fit the two links in the wiring centre: 12 to 3 (live for the orange valve cores) and 14 to 2 (neutral for the blue cores, the boiler and the pump).
  4. Power the R47 from terminals 1, 2 and 3. Then connect its outputs: Z1 ON to 4, Z2 ON to 5, Z3 ON to 6 and Z4 ON to 7.
  5. Wire the WRP: COM to 4 and N/O to 8.
  6. Wire the room thermostats on their COM and N/O terminals: CM2 (1) to 5 and 9, CM2 (2) to 6 and 10, and CM2 (3) to 7 and 11. Always use the N/O contact, which closes when the room calls for heat.
  7. Connect the valve motors. Run the brown cores to their own terminals: ZV1 to 8, ZV2 to 9, ZV3 to 10 and ZV4 to 11. All four blue cores go to 14.
  8. Connect the valve switches. All four orange cores go to 12, all four grey cores go to 13, and every valve earth goes to 1. Terminals 12, 13 and 14 each take several cores, so ferrule them and make sure every strand is clamped.
  9. Connect the boiler: L to 13, N to 14 and earth to 1. Do this only if the boiler manual agrees with this arrangement.
  10. Connect the circulating pump in parallel with the boiler: L to 13, N to 14 and earth to 1.
  11. Label every cable, tug-test every terminal, dress the cores neatly and refit all covers.

Testing and start-up

Before you apply power, check that there is earth continuity from terminal 1 to each valve, the boiler, the pump and the spur. Also check that there is no continuity between live and earth.

  • Switch on the spur. Measure about 230 V between 3 and 2, and between 3 and 1.
  • With every programmer channel OFF and all valves closed, you should read 0 V between 13 and 14. The boiler and pump should stay off.
  • Turn Z1 ON and turn the WRP up. You should read 230 V at terminal 4, then at 8, and ZV1 should drive open. When it is fully open, its orange–grey switch closes, terminal 13 goes live, and the boiler and pump start.
  • Turn the WRP down. ZV1 should close and terminal 13 should go dead, as long as no other valve is open.
  • Repeat the test for Z2 with CM2 (1) and ZV2, Z3 with CM2 (2) and ZV3, and Z4 with CM2 (3) and ZV4. Each time, confirm that the correct valve moves.
  • Finish by setting the clock and switching times on the programmer and the temperatures on each thermostat.

Safety notes

  • Every part of this system works at 230 V, including the thermostats and the valve switch cores. Treat terminals 2 to 14 as live whenever the spur is on.
  • Terminal 13 can be live from any valve switch even when the thermostat you are working on is off. If the boiler has its own permanent supply, isolate that as well before you work.
  • Never replace the 3 A fuse with a higher rating to cure nuisance blowing. Find the fault first.
  • Earth every valve, the boiler and the pump at terminal 1.

Troubleshooting

Symptom Probable Cause What to Check
Nothing works at all, and the programmer display is blank 3 A fuse blown, spur switched off, or the supply is not on terminals 2 and 3 Measure between 3 and 2 at the wiring centre: you should read about 230 V. If you read nothing, check the spur switch and the 3 A fuse, then the L and N connections.
A zone is ON at the programmer and the thermostat is turned up, but its valve never opens Thermostat wired to the wrong contact, or COM not on the matching programmer output When the thermostat calls for heat, measure from its COM terminal (4 to 7) to 14, then from its N/O terminal (8 to 11) to 14. Both should read 230 V. Move the wire to the N/O contact if needed.
The valve opens but the boiler and pump don't start Link 12–3 missing, or the orange or grey core not on 12 or 13 Measure 230 V between 12 and 14. With the valve fully open, terminal 13 should also read 230 V. If it doesn't, check the orange and grey terminations.
No valve moves even though 230 V reaches its brown core Link 14–2 missing or blue cores not landed on 14 With power off, check continuity from 14 to 2 and from 14 to each blue core. Refit the 14–2 link.
The wrong room heats up, or hot water comes on when a room calls Brown cores swapped between terminals 8 to 11, or a thermostat landed on the wrong pair Turn on one zone at a time and note which valve opens. Each brown core must match its thermostat's N/O terminal.
The boiler and pump run all the time, even with everything off A grey core landed on 12, terminals 12 and 13 bridged, or a valve switch stuck closed With all zones OFF, terminal 13 should read 0 V. Disconnect the grey cores one at a time to find the one that keeps it live.
Hot water heats even when Z1 is switched OFF WRP COM fed from permanent live on 3 instead of terminal 4 With Z1 OFF, measure terminal 4 to 14: you should read 0 V. Make sure the WRP COM is on 4 only.
The fuse blows as soon as a thermostat calls for heat The thermostat's N/O or a brown core is landed on neutral (terminal 14 or 2) Isolate the supply and trace the N/O wire of the thermostat that was calling. It must go to 8, 9, 10 or 11, never to 14.
There's 230 V on terminal 13 but the boiler still won't fire The boiler needs a volt-free contact or a permanent live instead of a switched live Check the boiler's wiring instructions and rewire its control input to suit.
The boiler locks out or overheats right after the heating switches off The boiler needs a pump overrun, but the pump is fed from 13 and stops immediately Check the boiler manual for overrun and permanent supply terminals. If required, wire the pump from the boiler's overrun output.
You feel a tingle from a valve or pipework, or an RCD trips occasionally A missing or loose earth at terminal 1, or a damaged core touching metal With power off, check continuity from terminal 1 to each valve, the pump and the boiler, and retighten every earth. Run an insulation test from live to earth.

Frequently Asked Questions (FAQs)


How do I know whether this diagram matches my EPH pack?
This diagram matches you if your pack is the hardwired 4-channel kit. That kit has an R47 programmer, a WRP pipe/cylinder thermostat, three CM2 room thermostats, four 2-port valves and a 14-terminal wiring centre, sold as CR4P, CR422P or CR428P. The wireless CombiPack4 is a different kit. It uses a battery-powered RFRP-OT thermostat that talks by radio to a mains-powered RF1A-OT receiver, which has its own small terminal block. If you have the wireless kit, follow the receiver's terminal layout instead.

Why are the thermostats wired at 230 V instead of low voltage?
The thermostats are wired at 230 V because in this system they act as mains switches. The R47 sends 230 V out of each channel's ON terminal to the thermostat's COM. When the room or cylinder needs heat, the thermostat closes COM to N/O, which sends that 230 V straight to the valve's brown motor core. So the cables to the CM2 and WRP thermostats must be mains-rated and earthed. Always isolate the spur before you open a thermostat.

What do the orange and grey valve cores do?
The orange and grey cores are the valve's end switch. The switch closes when the valve is fully open. Orange gets permanent live from terminal 12, which is linked to 3. Grey returns that live to terminal 13, which feeds the boiler and pump. All four valves' switches are wired in parallel, so the boiler and pump run whenever at least one zone is open and stop when the last valve closes. That way the boiler never fires against closed valves.

Why does the wiring centre need the 12–3 and 14–2 links?
The links share the incoming supply with the terminals that need it. Link 12–3 puts permanent live on terminal 12, which feeds the orange switch cores of all four valves. Link 14–2 puts neutral on terminal 14, the common neutral for the blue valve cores, the boiler and the pump. Without the first link the boiler can never be fired. Without the second, no valve motor can run.

Will this pack work with any boiler?
No, check your boiler's instructions first. The drawing assumes the boiler fires when it gets a switched live on terminal 13. Many boilers need something different: a permanent live supply, a pump overrun output that keeps the pump running after the burner stops, or a volt-free signal from the valve limit switches. In any of these cases, keep the valve and thermostat wiring as drawn but change the boiler and pump connections to match the boiler manufacturer's schematic.

What fuse rating should the supply have?
Supply the system from a fused spur with a 3 A fuse. That one spur powers the programmer, thermostats, valves, boiler control and pump through the wiring centre. If the fuse keeps blowing, treat it as a sign of a short or a miswired neutral, not as a reason to fit a bigger fuse. Uprating the fuse removes the protection the system relies on and can let a fault overheat the wiring.

Can I use the pack with fewer than four zones?
Yes, as a general practice you can leave a channel out. If you don't need a zone, don't fit its thermostat or valve, so its programmer output and its brown-core terminal simply stay unconnected. Don't connect a spare output to anything else, and don't bridge terminals to "complete" the circuit. Label the unused channel at the programmer so nobody expects it to do anything.

Can I wire the pump somewhere other than terminal 13?
Only if the boiler requires it. As drawn, the pump is wired in parallel with the boiler on terminals 13 and 14, so it runs whenever any valve is fully open. Some boilers have their own pump terminals or need a pump overrun after the burner stops. In that case, wire the pump to the boiler's pump or overrun output, as the boiler instructions show, rather than to 13.

Where should I mount the room thermostats?
Mount each room thermostat about 1.5 metres above the floor, in the zone it controls. Choose a spot where it can sense true room temperature: out of direct sunlight, and away from radiators, fires, appliances, drafts and outside doors. A badly placed thermostat makes its zone overheat or stay cold even when the wiring is perfect. Leave enough slack in the cable to remove the thermostat from its plate for servicing.

What are the electrical ratings of the wireless CombiPack4 receiver?
The RF1A-OT receiver runs on 200 to 240 Vac at 50 to 60 Hz. Its contact is rated 250 Vac 10(3)A, and it is a Class II, IP20 device. If you need a mains voltage output from its switching contact, terminals L and 2 must be linked. Never connect mains voltage to its OpenTherm terminals. Mount it within 20 metres of the thermostat and at least 1 metre from metal objects and other electronics.

Do I need a qualified person to install this pack?
Yes, a qualified person should do it. The installation involves 230 V wiring to a fused spur, several valves, a pump and the boiler's control circuit, and EPH says installation and connection should only be done by a qualified person. In many areas, new or altered heating control circuits also have to be notified or certified. A heating engineer can also confirm how your boiler wants to be interfaced.